| 110/190 | 3 | | T1-T12 | 50 Hz, 151 amperes, W12 tap H3 |
| 110/190 | 3 | Series Wye | | 50 Hz; 151 A; reference voltage wire (W12) tap H3 |
| 115/200 | 3 | | T1-T12 | 50 Hz, 142 amperes, W12 tap H4 |
| 115/200 | 3 | Series Wye | | 50 Hz; 142 A; reference voltage wire (W12) tap H4 |
| 115/230 | 1 | | T1-T12 | 50 Hz, 216 amperes, W12 tap H6 |
| 115/230 | 1 | Double Delta | | 50 Hz; 216 A; reference voltage wire (W12) tap H6 |
| 115/230 | 3 | | T1-T12 | 50 Hz, 125 amperes, W12 tap H6 |
| 115/230 | 3 | Series Delta | | 50 Hz; 125 A; reference voltage wire (W12) tap H6 |
| 120/208 | 3 | | T1-T12; L1, L2, L3; L0 neutral | 60 Hz, 174 amperes, W12 tap H3 |
| 120/208 | 3 | Series Wye | | 60 Hz; 174 A; reference voltage wire (W12) tap H3 |
| 120/240 | 1 | | T1-T12; L0 neutral (can be grounded), L1/L2 hot | 60 Hz, 260 amperes, reference voltage wire (W12) tap H5 |
| 120/240 | 1 | Double Delta | | 60 Hz; 260 A; reference voltage wire (W12) tap H5 |
| 120/240 | 3 | | T1-T12; L1, L2, L3; L0 neutral (can be grounded) | 60 Hz, 151 amperes, W12 tap H5 |
| 120/240 | 3 | Series Delta | | 60 Hz; 151 A; reference voltage wire (W12) tap H5 |
| 127/220 | 3 | | T1-T12 | 60 Hz, 164 amperes, W12 tap H4 |
| 127/220 | 3 | Series Wye | | 60 Hz; 164 A; reference voltage wire (W12) tap H4 |
| 139/240 | 3 | | T1-T12 | 60 Hz, 151 amperes, W12 tap H5 |
| 139/240 | 3 | Series Wye | | 60 Hz; 151 A; reference voltage wire (W12) tap H5 |
| 220/380 | 3 | | T1-T12 | 50 Hz, 76 amperes, W12 tap H3 |
| 220/380 | 3 | Series Wye | | 50 Hz; 76 A; reference voltage wire (W12) tap H3 |
| 230/400 | 3 | | T1-T12 | 50 Hz, 72 amperes, W12 tap H4 |
| 230/400 | 3 | Series Wye | | 50 Hz; 72 A; reference voltage wire (W12) tap H4 |
| 240/416 | 3 | | T1-T12 | 60 Hz, 87 amperes, W12 tap H3 |
| 240/416 | 3 | Series Wye | | 60 Hz; 87 A; reference voltage wire (W12) tap H3 |
| 254/440 | 3 | | T1-T12 | 60 Hz, 82 amperes, W12 tap H4 |
| 254/440 | 3 | Series Wye | | 60 Hz; 82 A; reference voltage wire (W12) tap H4 |
| 277/480 | 3 | | T1-T12 | 60 Hz, 75 amperes, W12 tap H5 |
| 277/480 | 3 | Series Wye | | 60 Hz; 75 A; reference voltage wire (W12) tap H5 |
| 347/600 | 3 | | factory connected | 60 Hz, 60 amperes, W12 tap H3; not reconnectible (code 9X) |
| 347/600 | 3 | Factory connected (nameplate voltage code 9X) | | 60 Hz; 60 A; H3 - Not Reconnectible; also nameplate voltage code 3R 120/240 made at factory |