Procedure

  1. Move the Run/Off/Auto switch to the Run position.
  2. Starter begins cranking; after a few seconds the engine starts and the starter disconnects.
  3. If engine does not start, the control indicates an overcrank shutdown.
  4. To clear overcrank, place Run/Off/Auto switch in Off and momentarily press Reset.
  5. Wait two minutes for the starter motor to cool, then repeat.

Specs & values

  • Cycle cranking: crank/rest 7 to 20 seconds individually preset; 3, 4, or 5 cycles
  • Continuous cranking up to 75 seconds

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DQBA →, Cummins/Onan DQBB →