Home›Repair guides›Cummins/Onan›Resetting the Control (PCC)

Cummins/Onan NTA855 — Resetting the Control (PCC)

Operation · PowerCommand Control 3100

For the Cummins/Onan NTA855, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DQBA, Cummins/Onan DQBB, Cummins/Onan NTA855, Cummins/Onan NT855 engine, Cummins/Onan NTA855 engine, Cummins/Onan N14 engine

Procedure

  1. Correct the condition that caused the fault.
  2. To reset a shutdown message, turn the Run/Off/Auto switch to Off position and press Reset.
  3. In Auto mode, reset warning by cycling the remote reset input after condition is corrected.
  4. In Auto mode, reset shutdown faults by removing remote start input, then cycling remote reset input.

Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DQBA →, Cummins/Onan DQBB →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.