Cummins/Onan NTA855 — Resetting the Control (PCC)
Operation · PowerCommand Control 3100
For the Cummins/Onan NTA855, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan DFBF, Cummins/Onan DFCB, Cummins/Onan DFCC, Cummins/Onan DFCE, Cummins/Onan DQBA, Cummins/Onan DQBB, Cummins/Onan NTA855, Cummins/Onan NT855 engine, Cummins/Onan NTA855 engine, Cummins/Onan N14 engine
Procedure
- Correct the condition that caused the fault.
- To reset a shutdown message, turn the Run/Off/Auto switch to Off position and press Reset.
- In Auto mode, reset warning by cycling the remote reset input after condition is corrected.
- In Auto mode, reset shutdown faults by removing remote start input, then cycling remote reset input.
Full service-parts list: Cummins/Onan DFBF →, Cummins/Onan DFCC →, Cummins/Onan DFCE →, Cummins/Onan DQBA →, Cummins/Onan DQBB →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.