Cummins/Onan — Normal Local Starting Procedure
Operation · Engine starting system
From a Cummins/Onan owner's manual covering: 6CTA8.3, CFP83-F10, CFP83-F20, CFP83-F30, CFP83-F40. Check it applies to your exact model before use.
Applies to: Cummins/Onan 6CTA8.3, Cummins/Onan CFP83-F10, Cummins/Onan CFP83-F20, Cummins/Onan CFP83-F30, Cummins/Onan CFP83-F40, Cummins/Onan 6CTA8.3G2 engine, Cummins/Onan 6CTAA8.3G3 engine
Before you start
- To prevent damage to the starter, do not engage the starting motor more than 15 seconds. Wait 15 seconds between each attempt to start.
Procedure
- Press the MANUAL position on the AUTO/MANUAL rocker switch.
- Observe the battery voltages displayed; use the battery with the highest indicated voltage.
- Start the engine using either the CRANK BATT A or CRANK BATT B rocker switch positions.
- Depress the selected switch for up to 15 seconds or until the engine starts; repeat up to three times if necessary.
- Check that engine oil pressure is indicated on the gauge within 15 seconds after starting.
- To stop, select the AUTO position on the AUTO/MANUAL rocker switch and press the RESET switch.
Specs & values
- Engine oil pressure must be indicated within 15 seconds after starting
Full service-parts list: Cummins/Onan CFP83-F10 →, Cummins/Onan CFP83-F20 →, Cummins/Onan CFP83-F30 →, Cummins/Onan CFP83-F40 →
Source: Cummins/Onan owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.