Cummins/Onan — Mode Setup (Remote and Standby)
Operation · Local display
From a Cummins/Onan service manual covering: C13 N6H, C13N6H, C17 N6H, C17N6H, C20 N6, C20N6H, RS13A. Check it applies to your exact model before use.
Applies to: Cummins/Onan C13 N6H, Cummins/Onan C17 N6H, Cummins/Onan C20 N6, Cummins/Onan RS13A
Before you start
- To prevent unexpected starts from remote devices, disable Remote mode and disconnect the connector on the back of the local display wired to any remote mounted displays.
Procedure
- From any screen, select the Mode key to get to the Mode screen.
- Use the arrow keys to enable or disable the Remote mode. Select the Next key to go to the next screen.
- Use the arrow keys to enable or disable the Standby mode.
- Keep pressing the Back button to save the settings and return to the Main screen.
- On the REMOTE display, select the Mode key and use the arrow keys to enable or disable Standby mode (Remote must be enabled first).
Specs & values
- Whenever Standby is enabled, the Remote mode is automatically enabled
- A manual Start or Stop event will disable the Standby function
Full service-parts list: Cummins/Onan C20 N6 →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.