Cummins/Onan — Megger and PI Test

Testing & diagnosis · Generator stator and rotor windings

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DQKB, Cummins/Onan DQKC, Cummins/Onan QSK60 engine

Before you start

  • Hazardous voltage. After DC test voltage applied, reconnect Grounding Cluster to remove static charge after each test.

Procedure

  1. Perform the Generator Set Grounding Procedure.
  2. Disconnect connector 10 from voltage regulator output stage and AC control leads 5,6,7,8.
  3. If RTD option installed, ground all six RTD temperature leads (18 leads total).
  4. Main Stator: remove and separate neutral leads from terminal 'N'.
  5. Connect megger between one stator phase and ground, grounding other two phases; test.
  6. Repeat stator test for the other two phases.
  7. Main Rotor: disconnect rotor and voltage suppressor leads from F1+ and F2-.
  8. Connect megger between one rotor lead and ground and conduct the test.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Megger test: 500 VDC for 600 VAC or less; 2500 VDC for 601-5000 VAC; 5000 VDC for 5001-15000 VAC
  • PI = 10-minute reading divided by 1-minute reading; ratio of two or greater is good

Full service-parts list: Cummins/Onan DQKB →, Cummins/Onan DQKC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.