Cummins/Onan M-1902s — Starting the Generator Set
Operation
For the Cummins/Onan M-1902s, from the Cummins/Onan service manual.
Applies to: Cummins/Onan HDKA, Kubota V1505-E3BG engine
Before you start
- Do not operate the generator set inside any room or building.
- Shut down immediately if an exhaust leak is discovered.
Procedure
- Hold Start/Stop/Preheat switch in Preheat position for 15 to 30 seconds, then hold in Start position.
- Monitor oil pressure, coolant temperature, and battery charge voltage gauges.
- Check exhaust system for leaks visually and audibly; shut down if leaks found.
- Check for fuel, oil, or coolant leaks; shut down and repair before more checks.
- Connect AC voltmeter and frequency meter across two line terminals; apply load and check output.