Cummins/Onan M-1902s — Compartment Construction
Installation · genset compartment
For the Cummins/Onan M-1902s, from the Cummins/Onan service manual.
Applies to: Cummins/Onan HDKA, Kubota V1505-E3BG engine
Before you start
- Make compartment walls vapor-tight to prevent exhaust fumes entering living quarters.
- Do not position muffler directly below drain hole. Do NOT use absorbent soundproofing on compartment floor.
Procedure
- Construct a vapor-tight wall to separate compartment area from living quarters and fuel supply.
- Line compartment walls with 26-gauge galvanized steel or comparable material.
- Construct compartment floor to prevent oil, fuel, or water accumulation.
- Provide holes for diesel fuel supply and return lines, breather hose exit, and exhaust plumbing.
- Install an approved junction box for connecting generator and load leads.
Specs & values
- Line compartment with self-extinguishing acoustical material 1/2 to 1 inch (12.7 to 25.4 mm) thick rated 250°F (121°C) minimum
Full service-parts list: Cummins/Onan HDKA →, Kubota V1505-E3BG engine →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.