From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15-G9 engine

Before you start

  • The generator set cannot be considered safe to work on until the engine is properly immobilized.

Procedure

  1. Press the Off mode switch on the operator panel to shut down the generator set.
  2. Press the Emergency Stop button to prevent the generator set starting, regardless of the Start signal source.
  3. Thoroughly ventilate the plant room before disconnecting any leads.
  4. Isolate and lock off the supply to the heater, where fitted.
  5. Isolate and lock off the supply to the battery charger, where fitted.
  6. Isolate the fuel supply to the engine.
  7. Using an insulated wrench, disconnect the negative (-) cable first on the starting batteries and control system batteries.
  8. Fit warning notices at each of the above points to indicate Maintenance in Progress - Plant Immobilized for Safe Working.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.