Cummins/Onan — Immobilize the Generator Set
Maintenance
From a Cummins/Onan service manual covering: C13 N6H, C13N6H, C17 N6H, C17N6H, C20 N6, C20N6H, RS13A. Check it applies to your exact model before use.
Applies to: Cummins/Onan C13 N6H, Cummins/Onan C17 N6H, Cummins/Onan C20 N6, Cummins/Onan RS13A
Before you start
- Accidental or remote starting of the generator set can cause severe personal injury or death.
Procedure
- Press the Off switch from the display and then press the E-Stop button to shut down the engine.
- Thoroughly ventilate the generator set before disconnecting any leads.
- Turn off and disconnect the heater (where fitted) from the AC source before disconnecting the battery cables.
- Turn off and disconnect the battery charger (where fitted) from the AC source.
- Turn off the fuel supply to the engine.
- Disconnect the battery. Disconnect the negative (–) cable first, using an insulated wrench.
- Place warning notices at each location that state, 'Maintenance in Progress – Immobilized for Safe Working.'
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Full service-parts list: Cummins/Onan C20 N6 →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.