Cummins/Onan — Governor Sensitivity and Droop Adjustment
For these Cummins/Onan models: MCE 4.5, MCE 5.0, MCE 6.5.
Applies to: Cummins Onan Mce 4 5, Cummins Onan Mce 5 0, Cummins Onan Mce 6 5
Before you start
- Disconnect load and readjust governor speed as necessary
- If set hunts, increase droop to maximum
Procedure
- 5. Also check governor response under 1/4, 1/2 and
- 6. Push the adjustment limiter cap on over the mixture
- 3. Connect rated load. Note that output voltage falls
Specs & torque values
- 62-63 Hertz frequency
- 51.5-52.5 Hertz
- 2 Hertz
- 4 Hertz maximum droop
- 1/4, 1/2, 3/4 rated loads
Source: manual:927-0505 Onan MCE Ensign series Marine Gensat Service Manual (09-1995).pdf. Figures and steps are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.