Cummins/Onan — Genset Ammeter Display Calibration (B)
Adjustments · PowerCommand control current display
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DFE
Before you start
- Contacting hazardous voltage components can cause electrocution, resulting in severe personal injury or death.
- Improper calibration or adjustment of the PowerCommand control can cause equipment malfunction or damage.
Procedure
- Display the Current Calibration submenu.
- With the genset OFF, attach a calibrated ammeter to L1.
- Start the genset and allow it to reach normal operating speed.
- Load the genset to maximum rated kVA at rated voltage.
- Calibrate the reading for L1 current so display agrees with calibrated ammeter.
- Repeat steps 2 through 5 for L2 and L3.
- Exit menu to Save changes.