Cummins/Onan — Generator Set Grounding Procedure

Maintenance · Generator output / stator windings

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DQKB, Cummins/Onan DQKC, Cummins/Onan QSK60 engine

Before you start

  • No person should attempt these procedures unless fully trained in medium voltage grounding procedures.

Procedure

  1. Open, lock-out and tag-out all sources of power to the work area.
  2. Disable starting system: disconnect battery charger, remove negative battery cable, install lockout device.
  3. Put on high voltage gloves with leather protectors.
  4. Using two pre-tested voltage detection devices, verify de-energized condition and retest detectors.
  5. Remove metal cover from generator output box to access generator load terminals.
  6. Securely install Grounding Cluster ground clamp to a verified grounded conductor.
  7. Leave grounds connected for one minute to ensure static charge dissipation.
  8. Remove ground cluster and perform PI and/or other required stator winding tests.
  9. When work is complete, remove the Grounding Cluster in reverse order of installation.
  10. After clearance from all personnel, remove all lock-out devices in reverse order of installation.

Tools required

  • High voltage gloves with leather protectors Amazon
  • Two pre-tested voltage detection devices Amazon
  • Grounding Cluster Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan DQKB →, Cummins/Onan DQKC →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →