Cummins/Onan — Generator Config Screen Setup

Adjustments · Control board

From a Cummins/Onan service manual covering: C13 N6H, C13N6H, C17 N6H, C17N6H, C20 N6, C20N6H, RS13A. Check it applies to your exact model before use.

Applies to: Cummins/Onan C13 N6H, Cummins/Onan C17 N6H, Cummins/Onan C20 N6, Cummins/Onan RS13A

Before you start

  • Failure to configure will result in Fault Code 37.

Procedure

  1. From the Main screen, select Menu.
  2. Press and hold the Next key on the Menu screen for at least 5 seconds to view the Config Menu.
  3. Highlight 'Config' and click the Enter key. The Generator Config screen appears.
  4. Use the Next key to navigate to the Config field. Use the arrow keys to select the appropriate config option (20 = C20N6H/C20N6HC, 21 = C17N6H, 22 = C13N6H).
  5. Use the Next key to navigate to the Fuel Type field. Select NG (natural gas; default) or LP (liquid propane).
  6. Keep selecting the Back button to save the settings and return to the Main screen.

Specs & values

  • Config 20: C20N6H, C20N6HC
  • Config 21: C17N6H
  • Config 22: C13N6H

Full service-parts list: Cummins/Onan C20 N6 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.