Cummins/Onan G1250s / M-1902s — Installation of Line Circuit Breakers in 50 Hz Generator Set

Installation

For the Cummins/Onan G1250s / M-1902s, from the Cummins/Onan service manual.

Applies to: Cummins/Onan HDKA, Kubota V1305-B engine

Before you start

  • Only a qualified electrician should make this installation.
  • Be sure to disconnect the generator set starting battery ground cable to prevent accidental starting.

Procedure

  1. Park the recreational vehicle on as level a surface as possible, lock the brakes, and remove the ignition key.
  2. Disconnect the generator set starting battery ground (-) cable at the battery.
  3. Remove the cover from the genset control box on the generator set.
  4. Mount the circuit breaker assembly in the control box using screws and washers that held the cover plate.
  5. Connect the generator output leads L1, L2, and L3 to the circuit breaker as illustrated on Page 11-4.
  6. Run the RV neutral lead into the control box and connect it to the ground connection.
  7. Connect the green lead from the genset and the green lead from the RV to the ground connection.
  8. Secure the conduit(s) to the control box and reconnect the starting battery ground cable.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan HDKA →, Kubota V1305-B engine →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.