Home›Repair guides›Cummins/Onan›Fuel Transfer Pump Control AC Connections (240 VAC to 120 VAC Conversion)

Cummins/Onan — Fuel Transfer Pump Control AC Connections (240 VAC to 120 VAC Conversion)

Adjustments · Day tank controller

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DFEJ, Cummins/Onan DFEK, Cummins/Onan QSX15-G9 engine

Before you start

  • The control is set up at the factory for connection to 240 VAC.

Procedure

  1. Remove the two jumpers between terminals TB1-6 and TB1-7 and connect one jumper between TB1-5 and TB1-6 and the other between TB1-7 and TB1-8.
  2. Move selector switch S103 on the control PCB to the up position for 120 V.
  3. On the control transformer, remove the two jumpers between terminals H2 and H3 and connect one jumper between H1 and H3 and the other between H2 and H4.
  4. Attach a tag to the control box indicating the supply voltage.

Specs & values

Full service-parts list: Cummins/Onan DFEJ →, Cummins/Onan DFEK →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.