Home›Repair guides›Cummins/Onan›Fuel Pump Control AC Connections

Cummins/Onan — Fuel Pump Control AC Connections

Installation

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF, Cummins/Onan QSM11 engine

Procedure

  1. To convert the day tank controller from 240 VAC to 120 VAC, remove the two jumpers between terminals TB1-6 and TB1-7 in the control box. Connect one between TB1-5 and TB1-6 and the other between TB1-7
  2. Move selector switch S103 on the control PCB to the up position for 120V.
  3. If the control is equipped with a transformer, remove the two jumpers between terminals H2 and H3. Connect one between H1 and H3 and the other between H2 and H4.
  4. To convert the day tank controller from 120 VAC to 240 VAC, remove the jumpers between TB1-5 and TB1-6, and TB1-7 and TB1-8. Connect the two jumpers between TB1-6 and TB1-7.
  5. Move selector switch S103 on the control PCB to the down position for 240 VAC.
  6. If the control is equipped with a transformer, remove the jumpers between H1 and H3, and H2 and H4. Connect the two jumpers between H2 and H3.
  7. Attach a tag to the control box indicating the supply voltage.
  8. Terminals TB1-8 and TB1-5 are available for connection of a 120 or 240 VAC electric fuel shutoff valve rated not more than 0.5 amps.

Specs & values

  • 120 VAC
  • 240 VAC
  • 0.5 amps

Full service-parts list: Cummins/Onan DQAD →, Cummins/Onan DQAE →, Cummins/Onan DQAF →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →