Cummins/Onan — Field Winding Tests
Testing & diagnosis · Field (frame) windings
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan MCCK
Before you start
- Attach and remove meter leads only when generator set is not operating.
Procedure
- Disconnect the field coil leads from their terminal points on the brush blocks.
- Disconnect the S1 terminal from the start solenoid.
- Ground test: touch one prod to each coil terminal and the other to a clean, paint-free part of the frame.
- If the lamp lights or ohmmeter shows continuity, replace the frame assembly.
- Open test: check the shunt winding resistance between S1 and F2.
- Measure the series winding resistances between S1 and S2, and S1 and S3.
- If resistance is high, an open circuit is likely and the frame assembly should be replaced.