Cummins/Onan — Evacuating the AC System
Maintenance
From a Cummins/Onan service manual covering: ES2075s, FS1870s, M11979s, M1976s, M1977s, M1978s. Check it applies to your exact model before use.
Applies to: Kubota 2482B engine
Procedure
- Make sure the AC hose fittings are secure at the evaporator and at the power unit.
- Attach a gauge set to the high pressure (HP) and low pressure (LP) sides at the quick connect access valves.
- Attach a vacuum pump to the center hose of the gauge set.
- Open the no load fitting on the pump housing, start the pump, open the manifold hand valves and close the no load fitting.
- Run the pump for five minutes, then close the hand valves and shut off the pump.
- Observe the gauge readings for a few minutes; if needles move up there is a leak.
- Check and tighten fittings, restart the pump and repeat the leak check.
- Run the vacuum pump for an hour to remove moisture from the system.
- After one hour, verify LP side reaches minus (-) 29 inches Hg and HP side reads less than zero PSI.
- Close the hand valves.
Tools required
Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.
Specs & values
- LP side: minus (-) 29 inches Hg
- HP side: less than zero PSI
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.