Cummins/Onan — Enabling Battle Short Mode (Installations With an Operator Panel)

Operation · PCC1302 control

From a Cummins/Onan service manual covering: 1302 series control, HMI211, HMI211RS, PCC 1302. Check it applies to your exact model before use.

Applies to: Cummins/Onan PCC 1302

Before you start

  • Use of the Battle Short mode feature can cause a fire or electrical hazard, resulting in severe personal injury or death and/or property and equipment damage. Operation of the genset must be supervised during Battle Short operation.

Procedure

  1. Use the PC service tool to enable the Battle Short mode feature.
  2. View the Service Menu by simultaneously holding down the "up" and "down" arrow keys.
  3. Select item 1, "Setup Menus".
  4. Enter setup menu password 574.
  5. Select item 1, "Genset Service".
  6. Select item 1, "Genset".
  7. Press the selection button five times to view the "Battleshort" menu.
  8. Press the ADJUST button and change the "Switch Input:" setting to "Operator Panel" or a customer input.
  9. Save the adjustments by pressing the "Save" button.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan PCC 1302 →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.