Cummins/Onan — Emergency Stop Reset
Operation · Emergency Stop button
From a Cummins/Onan owner's manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF, Cummins/Onan QSM11 engine
Procedure
- Pull the button out.
- Move the Run/Off/Auto switch to Off.
- Press the front panel Reset switch.
- Select Run or Auto, as required.
Specs & values
- Emergency Stop shutdown status (Code 102) can be reset only at the PCC front panel.
Full service-parts list: Cummins/Onan DQAD →, Cummins/Onan DQAE →, Cummins/Onan DQAF →
Source: Cummins/Onan owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.