Home›Repair guides›Cummins/Onan›Emergency starting procedure

Cummins/Onan — Emergency starting procedure

Operation · FPDP

From a Cummins/Onan owner's manual covering: CFP-015, CFP11E, CFP15E, CFP23E, CFP30E, CFP50, CFP59, CFP5E, CFP60E, CFP7E, CFP83, CFP83-F10…. Check it applies to your exact model before use.

Applies to: Cummins/Onan CFP23E, Cummins/Onan CFP83-F10, Cummins/Onan CFP83 engine

Before you start

  • Do not engage the starting motor more than fifteen seconds. Wait fifteen seconds between attempts, up to six attempts.
  • Engine oil pressure must be indicated on the gauge within fifteen seconds after starting.

Procedure

  1. Open the water bypass valves in the cooling water supply piping or emergency cooling supply.
  2. Press the AUTO/MAN selector switch on the FPDP to place the engine in MANUAL mode.
  3. Open the FPDP panel door and slide the key switch override to the RIGHT position; verify LED 49 - KEY FB is lit.
  4. Press downward on either the Battery A or Battery B contactor lever to start the engine.
  5. If crank contactor lever A does not engage, repeat using crank contactor lever B.
  6. If battery charge is low, press both battery contactor levers at the same time; release immediately after the engine starts.
  7. Check that the engine starts and operates at the rated speed.

Full service-parts list: Cummins/Onan CFP23E →, Cummins/Onan CFP83-F10 →

Source: Cummins/Onan owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.