Home›Repair guides›Cummins/Onan›Emergency Start-Stop Operation

Cummins/Onan — Emergency Start-Stop Operation

Operation · Control board

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MCCK

Before you start

  • This emergency operation does NOT provide fuse protection, start disconnect or low oil pressure shutdown, and should not be used without monitoring the generator set.

Procedure

  1. Connect a jumper between terminals 9 and 11 to energize ignition, fuel solenoid and fuel pump.
  2. Temporarily jumper terminals 1 and 7 to energize starter.
  3. Remove this jumper as soon as the engine starts and runs.
  4. Do not jumper these terminals while the engine is running.
  5. To stop the genset, remove the jumper from terminals 9 and 11.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan MCCK →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Cummins/Onan repair guides →