Cummins/Onan — Complete System Test

Operation · Transfer switch / generator set

From a Cummins/Onan service manual covering: C13 N6H, C13N6H, C17 N6H, C17N6H, C20 N6, C20N6H, RS13A. Check it applies to your exact model before use.

Applies to: Cummins/Onan C13 N6H, Cummins/Onan C17 N6H, Cummins/Onan C20 N6, Cummins/Onan RS13A

Before you start

  • Only authorized and qualified maintenance technicians should carry out this test.

Procedure

  1. Before starting, check the oil level and make sure there is enough fuel.
  2. Place the generator set in Standby mode.
  3. Switch the main utility disconnect from the ON to the OFF position.
  4. Make sure the generator set starts and, after it stabilizes, the load is transferred from the utility to the generator set.
  5. Switch the main utility disconnect from the OFF to the ON position.
  6. Make sure that after approximately 5 minutes the load is transferred back to the utility.
  7. Make sure that once the transfer switch is connected to utility power, after approximately 5 minutes, the generator set stops.

Specs & values

  • Utility re-transfer delay: approximately 5 minutes
  • Generator set cool down: approximately 5 minutes