Home›Repair guides›Cummins/Onan›Changing Genset Frequency (50/60 Hz)

Cummins/Onan — Changing Genset Frequency (50/60 Hz)

Adjustments · Voltage regulator / governor

From a Cummins/Onan service manual — check it applies to your exact model before use.

Applies to: Cummins/Onan MDKUB, Cummins/Onan MDKWB

Before you start

  • Disconnect starting battery positive terminal first to disable the genset before adjustments

Procedure

  1. Turn the generator set off and open the control box
  2. Move the 60 Hz/50 Hz switch on the regulator board to the desired value
  3. Remove all load and connect a frequency meter across the output
  4. Loosen and back off the lock nuts on the speed adjustment screws
  5. Turn the set on with no load and adjust low/high speed screws per conversion direction
  6. Tighten lock nuts once target frequency is reached (53 Hz or 63 Hz stop points)
  7. Center the voltage adjustment pot and adjust output voltage to rated value ± 5 VAC
  8. Fine tune output voltage with the faceplate pot and recheck

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Full service-parts list: Cummins/Onan MDKUB →, Cummins/Onan MDKWB →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.