Cummins/Onan — Battery Cable Connections at the Generator Set

Installation · battery cables

From a Cummins/Onan service manual covering: 5.5 HGJAA, 5.5 HGJAB, 6.5 HGJAA, 6.5 HGJAB, 7.0 HGJAA, 7.0 HGJAB. Check it applies to your exact model before use.

Applies to: Cummins/Onan HGJAA, Cummins/Onan HGJAB

Before you start

  • Routing battery cables with fuel lines can lead to fire and severe personal injury or death. Keep battery cables away from fuel lines.
  • Arcing can ignite the explosive hydrogen gas given off by the battery.

Procedure

  1. Terminate the battery cables with ring terminals sized for 5/16 inch screws and connect them to the generator set.
  2. Secure the insulating boot on the positive (+) terminal and tie it to the battery cable with the tie-wrap supplied with the manuals.
  3. Torque the positive (+) cable terminal to 6 Nm (4.5 ft-lbs).
  4. Torque the negative (–) cable terminal to 11 Nm (8 ft-lbs).
  5. When required, connect the grounding screw to the vehicle frame with No. 8 AWG or larger stranded cable and a ring terminal for a 3/8 inch screw; torque to 11 Nm (8 ft-lbs).

Specs & values

  • Positive (+) cable terminal: 6 Nm (4.5 ft-lbs)
  • Negative (–) cable terminal: 11 Nm (8 ft-lbs)
  • Grounding screw: 11 Nm (8 ft-lbs)
  • Cable size per Battery Cable Sizes table (2 AWG for 0-13.7 m / 0-45 ft)

Full service-parts list: Cummins/Onan HGJAA →, Cummins/Onan HGJAB →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.