Cummins/Onan — Adjusting Start/Stop Delays (PCC Adjust Menu)
Adjustments · controller
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF, Cummins/Onan QSM11 engine
Procedure
- Press button next to ADJUST in Main Menu to display VOLTAGE submenu
- Press button next to >> to move through FREQUENCY submenu to STOP DELAY submenu
- Use buttons next to arrows to set start delay, range 0 to 300 seconds
- Use buttons next to arrows to set stop delay, range 0 to 600 seconds
- Press >> to move to SAVE/EXIT submenu and select SAVE to retain changes, then EXIT
Specs & values
- start delay 0-300 seconds
- stop delay 0-600 seconds
Full service-parts list: Cummins/Onan DQAD →, Cummins/Onan DQAE →, Cummins/Onan DQAF →
Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.