Cummins/Onan — Adjust Start and Stop Delays
Adjustments · PowerCommand 3100 Control
From a Cummins/Onan service manual — check it applies to your exact model before use.
Applies to: Cummins/Onan DQAD, Cummins/Onan DQAE, Cummins/Onan DQAF, Cummins/Onan QSM11 engine
Procedure
- Press the button next to the word ADJUST in the Main Menu. The VOLTAGE submenu will appear.
- Press the button next to the '>>' to move through the VOLTAGE and FREQUENCY submenus to the START DELAY submenu.
- Use the buttons next to the '⇑' and '⇓' symbols to set the start delay. The start delay adjustment range is 0 to 300 seconds.
- From the START DELAY submenu, press the button next to the '>>' to move to the STOP DELAY submenu.
- Use the buttons next to the '⇑' and '⇓' symbols to set the stop delay. The stop delay adjustment range is 0 to 600 seconds.
- From the STOP DELAY submenu, press the button next to the '>>' to move to the SAVE/EXIT submenu. Select SAVE to save your changes.
- At the CHANGES SAVED submenu, select EXIT to return to the Main menu.
Specs & values
- Start delay adjustment range 0 to 300 seconds
- Stop delay adjustment range 0 to 600 seconds