Cummins/Onan A052J727 — Starting the Generator Set
Operation
For the Cummins/Onan A052J727, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan MDKD
Before you start
- Excessive cranking can burn out the starter or flood the engine (exhaust flow during cranking is too low to expel water from a wet exhaust system).
Procedure
- Visually check for water, coolant, fuel, and exhaust leaks.
- Push and hold start on control switch or digital display until the set starts.
- Let engine warm up two minutes before connecting large loads or engaging PTO.
- Monitor generator set status using the digital display.
- If start fails, cranking discontinues in 20 to 60 seconds; Fault Code No. 4 shown.
- If the set shuts down, note the numeric fault code and refer to troubleshooting.
Full service-parts list: Cummins/Onan MDKD →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.