Cummins/Onan 80MDKAL11454B — Starting at Set

Operation · generator set

For the Cummins/Onan 80MDKAL11454B, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan MDKAL, Kubota D1005 engine

Before you start

  • Excessive cranking can overheat the starter, damaging it.
  • exhaust gas is deadly; carbon monoxide can cause unconsciousness and death

Procedure

  1. Hold the starting switch to the STOP/PREHEAT position for 5 to 20 seconds, depending on temperature (Table 2).
  2. Release the switch, then move it to the START position.
  3. The starter will crank and after a few seconds the engine should start; starter disconnects automatically when generator AC voltage builds up.
  4. If the engine does not start after cranking 20 seconds, release the switch. Wait two minutes, then repeat the preheat step.
  5. If the engine does not start on the second attempt, check the fuel supply and make sure the fuel system has been primed.

Specs & values

  • Preheat time 5 to 20 seconds depending on temperature (Table 2)
  • Maximum cranking 20 seconds; allow two minutes for starter cooling
  • Preheat time longer than 20 seconds may damage glow plugs

Full service-parts list: Cummins/Onan MDKAL →, Kubota D1005 engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.