Cummins/Onan 80MDKAL11454B — Starting at Set
Operation · generator set
For the Cummins/Onan 80MDKAL11454B, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan MDKAL, Kubota D1005 engine
Before you start
- Excessive cranking can overheat the starter, damaging it.
- exhaust gas is deadly; carbon monoxide can cause unconsciousness and death
Procedure
- Hold the starting switch to the STOP/PREHEAT position for 5 to 20 seconds, depending on temperature (Table 2).
- Release the switch, then move it to the START position.
- The starter will crank and after a few seconds the engine should start; starter disconnects automatically when generator AC voltage builds up.
- If the engine does not start after cranking 20 seconds, release the switch. Wait two minutes, then repeat the preheat step.
- If the engine does not start on the second attempt, check the fuel supply and make sure the fuel system has been primed.
Specs & values
- Preheat time 5 to 20 seconds depending on temperature (Table 2)
- Maximum cranking 20 seconds; allow two minutes for starter cooling
- Preheat time longer than 20 seconds may damage glow plugs
Full service-parts list: Cummins/Onan MDKAL →, Kubota D1005 engine →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.