Cummins/Onan 80MDKAL11454B — Returning the Genset to Service

Maintenance · generator set

For the Cummins/Onan 80MDKAL11454B, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan MDKAL, Kubota D1005 engine

Before you start

  • Battery electrolyte can cause severe eye damage and burns to the skin; wear goggles, rubber gloves and a protective apron.
  • DO NOT OVERCHARGE the battery.

Procedure

  1. Remove plug from the exhaust outlet, and open the sea cock.
  2. Check tag on oil base and verify that oil viscosity is still correct for existing ambient temperature.
  3. Clean and check the battery; measure electrolyte specific gravity with a hydrometer (1.260 at 80 F [27 C]) and verify proper level; charge if low.
  4. Prime the fuel system.
  5. Connect the starting battery, negative (-) cable last.
  6. Remove all loads before starting the genset.
  7. After starting, run the generator set at no load for roughly 30 seconds, then apply a load of at least 50 percent rated capacity.
  8. Check all gauges for normal readings.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Specific gravity 1.260 at 80 F (27 C)
  • Run at no load roughly 30 seconds, then apply load of at least 50 percent rated capacity