Home›Repair guides›Cummins/Onan›Flushing and Cleaning the Cooling System

Cummins/Onan 80MDKAL11454B — Flushing and Cleaning the Cooling System

Maintenance · cooling system / heat exchanger

For the Cummins/Onan 80MDKAL11454B, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan MDKAL, Kubota D1005 engine

Before you start

  • Never pour hot water into a cold engine or cold water into a hot engine; this can crack the head or cylinder block.
  • Do not operate the unit without water for even a few minutes.
  • Contact with hot coolant can cause severe burns.

Procedure

  1. Drain the system by opening the heat exchanger drain and the cylinder block drain on the left side of the engine; drain completely and avoid spillage into bilge.
  2. If rust and scale have collected in the water jacket or heat exchanger, clean with a good cleaning compound following its instructions.
  3. After cleaning, drain the system and fill with clean water.
  4. Run the genset for 10 minutes, then drain the system completely.
  5. Refill with the 50/50 coolant mixture.

Specs & values

  • Run 10 minutes for flushing

Full service-parts list: Cummins/Onan MDKAL →, Kubota D1005 engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.