Cummins/Onan 50.0 DDB 15R / 50.0 DDB 15R J 1 Q — Starting the Generating Set
Operation
For the Cummins/Onan 50.0 DDB 15R / 50.0 DDB 15R J 1 Q, from the Cummins/Onan operator's manual.
Applies to: Cummins/Onan 50.0 DDB 15R, John Deere 6329D engine
Before you start
- Verify electric solenoid valve for city water cooled plants is open before initial start to allow coolant chambers to fill; overheating and engine damage could result.
Procedure
- Recheck that crankcase is filled.
- Recheck cooling system is filled and input solenoid valve open.
- Recheck batteries are charged and connected.
- Recheck fuel solenoid valve open.
- Move the run-stop/reset-remote switch to the run position.
- Immediately after start, observe oil pressure gauge; normal oil pressure is 45 to 65 psi (310.5 to 448.5 kPa).
- Check DC ammeter (10 to 30 amperes), AC voltmeter, and frequency meter.
Specs & values
- Normal oil pressure 45 to 65 psi (310.5 to 448.5 kPa)
Full service-parts list: Cummins/Onan 50.0 DDB 15R →, John Deere 6329D engine →
Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.