Home›Repair guides›Cummins/Onan›Dilute Battery Electrolyte for Hot Locations

Cummins/Onan 50.0 DDB 15R / 50.0 DDB 15R J 1 Q — Dilute Battery Electrolyte for Hot Locations

Maintenance

For the Cummins/Onan 50.0 DDB 15R / 50.0 DDB 15R J 1 Q, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan 50.0 DDB 15R, John Deere 6329D engine

Before you start

  • Do not attempt to pour off electrolyte; avoid skin or clothing contact.

Parts for this job

  • 416-0531 Battery — Cummins/Onan 50.0 DDB 15R Amazon eBay

Part numbers from the service-parts lists for Cummins/Onan 50.0 DDB 15R, John Deere 6329D engine. Verify against your serial number before ordering; some links are affiliate links.

Procedure

  1. Fully charge the battery.
  2. With the battery still on charge, draw off the electrolyte above the plates in each cell using a hydrometer or filler bulb.
  3. Refill each cell with distilled water to normal level.
  4. Continue charging for 1 hour at 4 to 6 amperes.
  5. Test each cell; if specific gravity is still above 1.225, repeat steps 2, 3 and 4 until reduced to 1.225.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Dilute electrolyte from 1.260 to 1.225 specific gravity when ambient is above 90F (32.2C)

Full service-parts list: Cummins/Onan 50.0 DDB 15R →, John Deere 6329D engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.