Cummins/Onan 50.0 DDB 15R / 50.0 DDB 15R J 1 Q — Control Box Connections (Generator Voltage Reconnection)

Installation · Control box / generator leads

For the Cummins/Onan 50.0 DDB 15R / 50.0 DDB 15R J 1 Q, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan 50.0 DDB 15R, John Deere 6329D engine

Before you start

  • Proceding instructions do not apply to models with a 347/600 voltage (designated 9X) or a 120/240 voltage (designated 3R); these connections are made at the factory.

Procedure

  1. Factory ships these 12 lead generators with load connection wires not connected together; wires T1 through T12 must be brought together before making load connections.
  2. Remove either right, left or top panel from control box.
  3. Connect wires together as shown on panel and in Figure 13 according to voltage desired.
  4. Open hinged control panel doors. Connect lead from terminal 63 to correct terminal (H2, H3, H4, H5 or H6) for voltage desired.
  5. Close front panel and secure with 1/4 turn fasteners.
  6. Connect load wires to generator leads.

Full service-parts list: Cummins/Onan 50.0 DDB 15R →, John Deere 6329D engine →

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.