Cummins/Onan 4.0BGEFA261 OOL / 4.0BGEFA26100L — Starting

Operation · Genset

For the Cummins/Onan 4.0BGEFA261 OOL / 4.0BGEFA26100L, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan EM (SN5782U1G2RA) engine

Before you start

  • An operating genset can ignite flammable vapors causing severe personal injury or death; NEVER start when docked for fueling.

Procedure

  1. Perform pre-start checks and turn off air conditioner and other large electrical loads.
  2. Turn on genset compartment evacuator blower at least four minutes to remove gasoline vapors.
  3. Push and hold genset or remote START switch until genset starts.
  4. Do not crank more than 10 seconds at a time; wait at least 30 seconds before retrying.
  5. Let genset warm up a few minutes until running smoothly before connecting electrical loads.
  6. Check for fuel and exhaust leaks; stop genset immediately if a leak is found and repair before continued operation.

Specs & values

  • Do not crank longer than 10 seconds at a time
  • Wait at least 30 seconds before trying again
  • Blower on at least 4 minutes before starting

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.