Cummins/Onan 4.0 MCCK / 6.5 MCCK — Returning Unit to Service

Maintenance · Generating set

For the Cummins/Onan 4.0 MCCK / 6.5 MCCK, from the Cummins/Onan operator's manual.

Applies to: Cummins/Onan MCCK engine

Before you start

  • Do not smoke while servicing batteries. Explosive gases are emitted from batteries in operation.

Procedure

  1. Remove cover and all protective wrapping; remove plug from exhaust outlet.
  2. Check tag on oil base and verify oil viscosity is still correct for existing ambient temperature.
  3. Clean and check battery; measure specific gravity and verify level to split ring; charge/add distilled water if required.
  4. Open fuel line.
  5. Connect batteries.
  6. Check coolant level and add as required.
  7. Verify that no loads are connected to the generator.
  8. Start engine.
  9. Check sea water pump operation.
  10. Apply load to at least 50 percent of rated capacity.
  11. Check all gauges for proper reading.

Source: Cummins/Onan operator's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.