Cummins/Onan 1750DQKB / 3200 Series — Generator/PCC Control Isolation Procedure

Testing & diagnosis · Generator / PCC control

For the Cummins/Onan 1750DQKB / 3200 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DFE

Before you start

  • This test involves unregulated excitation of the generator. To prevent damage due to overcurrent, make sure all loads are disconnected and all faults cleared from the generator output terminals.
  • HAZARDOUS VOLTAGE. Touching uninsulated parts inside the control housing and power output boxes can result in severe personal injury or death.

Procedure

  1. Throw the line circuit breaker OFF and shut down the set.
  2. Open the control box and remove plug 10 from connector 10 of the voltage regulator output module (A37).
  3. Prepare to measure output voltage across the generator terminals while the set is running.
  4. Bring two jumpers from a 12 volt battery for connection to the X (Field +) and XX (Field -) pins of plug 10.
  5. Check polarity again; polarity must be correct or the test will be inconclusive.
  6. Start the set and connect the jumper from the battery negative (-) terminal to the XX lead.
  7. If rated output voltage or higher is obtained and voltages are balanced, the generator circuitry is probably okay.

Tools required

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Normal excitation voltage ranges from approximately 10 VDC at no-load to approximately 40 VDC at full-load
  • X = Red wire of connector 10-6
  • XX = Brown wire of connector 10-3

Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.