Cummins/Onan 1750DQKB / 3200 Series — Generator Mount Pre-Load Adjustment

Adjustments · Generator mount / vibration isolators

For the Cummins/Onan 1750DQKB / 3200 Series, from the Cummins/Onan service manual.

Applies to: Cummins/Onan 1750DQKB, Cummins/Onan DFE

Before you start

  • Accidental starting of the generator set during this procedure presents the hazard of severe personal injury or death.

Procedure

  1. Turn off and disconnect battery charger (if equipped).
  2. Disconnect the negative (-) battery cable(s) to prevent accidental starting.
  3. Unscrew bolt (Item 2) from skid but do not remove it from either rear engine vibration isolator.
  4. Loosen the three screws that secure the engine mount brackets to the engine.
  5. Loosen but do not remove the hex nut (Item 1) from the M20 screw of the generator vibration isolators.
  6. Lift the generator until the mounting feet brackets are high enough to insert a 1 3/4 inch steel spacer under both stator foot brackets.
  7. Insert spacers and lower the generator so the full weight rests on the mounting foot brackets.
  8. Make sure no gap is present between the skid and the lower mount of the rear engine vibration isolators; tighten the three screws to 190-200 ft-lbs.
  9. Lift the generator to remove the two 1 3/4 inch steel spacers.
  10. Before lowering, start the threads of the rear engine vibration isolator bolts (Item 2).
  11. Lower the generator and tighten the two rear engine vibration isolator bolts to 270-330 ft-lbs.
  12. Secure the generator foot brackets to the vibration isolators; tighten the fastener to 270-330 ft-lbs.

Tools required

  • two 1 3/4 inch T x 2 inch W x 6 inch L steel spacers Amazon
  • adequate lifting device Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • engine mount bracket screws: 190-200 ft-lbs (260-270 FridayParts $22.00 N-m)
  • rear engine vibration isolator bolts: 270-330 ft-lbs (365-447 N-m)
  • generator foot bracket fastener: 270-330 ft-lbs (365-447 N-m)

Full service-parts list: Cummins/Onan 1750DQKB →, Cummins/Onan DFE →

Source: Cummins/Onan service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.