Caterpillar — Test Step 18. Check the Voltage at the ECM

Testing & diagnosis · Engine ECM connector P1

From a Caterpillar service manual covering: 3500B Engine, PM3516, PM3516 Power Module. Check it applies to your exact model before use.

Applies to: Caterpillar 3500B engine

Before you start

  • The status screen on the ET displays INVALID DATA when the ECM reads a signal that is out of range.

Procedure

  1. Turn the ECS to the OFF/RESET position, then ON with engine OFF.
  2. Measure analog voltage between suspect sensor signal voltage and sensor return at ECM P1.
  3. Observe the sensor reading on the ET status screen.
  4. Turn ECS OFF/RESET, then ON with engine OFF.
  5. Measure frequency and duty cycle between digital sensor signal and return at ECM P1.
  6. Start the engine and observe the ET status screen.

Tools required

  • ET (Electronic Technician) Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Analog signal voltage 0.2 to 0.6 VDC
  • Frequency 150 Hz to 1000 Hz
  • Duty cycle 10-21% below 49 °C, 22-88% between 49 °C and 851 °C, 80-90 FridayParts $32.86% above 851 °C
  • ET should read 30 °C (86 °F) while engine is cold

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.