The Caterpillar 3500B is an engine. It powers generator sets from Caterpillar, including the PM3516.
Also known as: Caterpillar 3500B
Compiled from service & troubleshooting documentation across every generator set that uses the Caterpillar 3500B.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Digital sensor duty cycle above 851 °C (1564 °F) | 80% to 90% | % | temperature above 851 °C (1564 °F) |
| Other | Digital sensor duty cycle below 49 °C (120 °F) | 10% to 21% | % | temperature below 49 °C (120 °F) |
| Other | Digital sensor duty cycle between 49 °C (120 °F) and 851 °C (1564 °F) | 22% to 88% | % | temperature between 49 °C (120 °F) and 851 °C (1564 °F) |
| Other | Digital sensor frequency reading between pin C and pin B | 150 to 1000 | Hz | all digital sensors |
| Pressure | Pressure drop shown on ET | 5 ± 2 | kPa | 0.7 ± 0.3 psi |
| Pressure | Vacuum pulled on differential pressure gauge | 5 ± 2 | kPa | 0.7 ± 0.3 psi |
| Resistance | Resistance between suspect sensor signal wire and supply voltage / return line / engine ground at ECM connector | greater than 20,000 | Ohms | ECM connectors J1/P1 and J2/P2 and suspect sensor disconnected |
| Resistance | Resistance through the harness (signal wire to supply, signal wire to return) | less than 10 | Ohms | ECM connectors J1/P1 and J2/P2 and suspect sensor connector disconnected |
| Temperature | Exhaust temperature reading with cold engine on ET | 30 | °C | 86 °F; engine cold |
| Temperature | Temperature reading variance when below 0 °C (32 °F) | 15 | °C | temperature below 0 °C (32 °F); 59 °F |
| Voltage | Analog sensor signal voltage between pin C and pin B | 0.2 to 4.5 | VDC | all analog sensors |
| Voltage | Analog sensor supply voltage (regulated by ECM) | 5.0 ± 0.5 | VDC | all analog sensors |
| Voltage | Analog sensor supply voltage at ECM, P1-36 (997-OR) to P1-30 (993-BR) | 5.0 ± 0.5 | VDC | ECS ON, engine OFF |
| Voltage | Digital sensor supply voltage (regulated by ECM) | 8.0 ± 0.5 | VDC | all digital sensors |
| Voltage | Digital sensor supply voltage at ECM, P1-35 (700-OR) to P1-29 (998-BR) | 8.0 ± 0.5 | VDC | ECS ON, engine OFF |
| Voltage | Suspect analog sensor signal voltage at ECM connector P1 | 0.2 to 0.6 | VDC | ECS ON, engine OFF |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Cat DEAC | Diesel; 3,000 Service Hours or Three Years; annual S·O·SSM Level 2 coolant sampling and analysis | |||
| Coolant | Cat ELC | Diesel; 12,000 Service Hours or Six Years; add Cat ELC Extender at 6,000 service hours or one half of service life; annual S·O·SSM Level 2 coolant sampling and analysis | |||
| Coolant | Cat NGEC | Natural Gas; 16,000 Service Hours or Three Years; use interval that occurs first | |||
| Engine oil | Cat NGEO | Natural Gas | |||
| Engine oil | Cat Arctic DEO SYN SAE 0W-30 | -40°C to 30°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SYN SAE 5W-40 | -30°C to 50°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SAE 10W-30 | -18°C to 40°C | Engine Crankcase; Industrial Engines | ||
| Engine oil | Cat DEO SAE 15W-40 | -9°C to 50°C | Engine Crankcase; Industrial Engines | ||
| Grease | Cat Generator Set Grease | Part Number 108-8611 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Disconnecting the Atmospheric Pressure Sensor will cause several sensor diagnostic codes to become active. Troubleshoot the original code.
Tools: 6V-9130 Temperature Adapter, Vacuum pump test unit, Differential pressure gauge, ET (Electronic Technician)
Tools: Jumper wire with socket terminals
⚠ Disconnecting the Atmospheric Pressure Sensor will cause several sensor diagnostic codes to become active. Troubleshoot the original code.
Tools: Suitable piece of wire
⚠ The status screen on the ET displays INVALID DATA when the ECM reads a signal that is out of range.
Tools: ET (Electronic Technician)
Tools: ET (Electronic Technician)
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Caterpillar 3500B powers 1 generator set(s), including Caterpillar PM3516.
A commonly reported issue on generators using the Caterpillar 3500B is: Voltage is out of range at the sensor connector.. Fix: Check and correct the voltage between pin A and pin B for the suspect sensor. The supply voltage should reach 5.0 + 0.5 VDC for all analog sensors and 8.0 + 0.5 for all digital sensors..