Caterpillar C15 / C15 Generator Set — Insulation - Test (Recommended Procedure for A Periodic Insulation Test)

Testing & diagnosis · Generator stator winding

For the Caterpillar C15 / C15 Generator Set, from the Caterpillar owner's manual.

Applies to: Caterpillar C15, Caterpillar C1.5 engine

Before you start

  • The high voltage that is produced by an operating generator set can cause severe injury or death.
  • The megohmmeter is applying a high voltage to the circuit. Do not touch the instrument leads without first discharging them.

Procedure

  1. Take the generator out of service.
  2. Visually inspect the generator for moisture. If moisture exists, dry the unit first.
  3. Discharge the capacitance of the windings.
  4. Isolate the stator windings by disconnecting all other leads and cables from the generator terminals.
  5. Connect the insulation tester's RED lead to ground.
  6. Connect the insulation tester's BLACK lead to the wye point of the generator's windings.
  7. Set the voltage to 500 Volts for units of 600 volts or less; 1000 Volts for units more than 600 volts.
  8. Apply voltage and observe readings at 30 seconds and 60 seconds. Record the 60 second reading, temperature and humidity.

Tools required

  • 142-5055 Insulation Testing Gp Amazon
  • 9U-6003 Insulation Testing Gp Amazon

Tool links are Amazon searches (affiliate links); manufacturer special tools may only be available from a dealer.

Specs & values

  • Minimum acceptable insulation resistance 1 megohm for generators below 1000 V.

Full service-parts list: Caterpillar C15 →

Source: Caterpillar owner's manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.