Home›Repair guides›Caterpillar›Event Clearing (Procedure For Clearing Events)

Caterpillar 3516 / EMCP 3 — Event Clearing (Procedure For Clearing Events)

Operation · EMCP3 event log

For the Caterpillar 3516 / EMCP 3, from the Caterpillar service manual.

Applies to: Caterpillar 3516, Caterpillar EMCP 3, Caterpillar 3516B engine

Procedure

  1. Press the STOP key to shut down the engine. Enter the EVENT LOG option from the main menu.
  2. Select an ECM from the list.
  3. Scroll through the event conditions to highlight the active events.
  4. Repair the condition that caused the shutdown event.
  5. Press the ENTER key. RESET will be highlighted if the condition is gone and control is in STOP.
  6. Press ENTER again. The fault clears and the red shutdown light turns off.
  7. Press the ESCAPE key 2 times to return to the main menu.

Full service-parts list: Caterpillar 3516 →, Caterpillar EMCP 3 →

Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.

More Caterpillar repair guides →