Caterpillar 3516 / EMCP 3 — Electronic Control Module (Generator Set) - Configure
Adjustments · EMCP3 generator set ECM setpoints
For the Caterpillar 3516 / EMCP 3, from the Caterpillar service manual.
Applies to: Caterpillar 3516, Caterpillar EMCP 3, Caterpillar 3516B engine
Before you start
- Ensure that the fault protection timer is ENABLED for events that will cause a SHUTDOWN EVENT during Start-Up (LOW OIL PRESS, UNDER VOLTAGE, UNDER FREQ, UNDER SPEED).
Procedure
- From main menu highlight PREFERENCES; set CONTRAST, BACKLIGHT, PRESSURE, TEMPERATURE, VOLUME, and LANGUAGE.
- Press ESCAPE to return to the main menu and highlight CONFIGURE.
- Press DOWN until SETPOINTS is highlighted.
- Scroll to AUTOMATIC START/STOP and adjust setpoints to desired values.
- Highlight ENG COOL TEMP; select Data Link for ADEM3/ADEM4 or I/O PIN otherwise.
- Highlight ENG OIL PRES MONITOR; select I/O PIN or Data Link.
- Highlight ENG SPEED MONITOR and input the flywheel teeth number.
- Highlight GEN AC MONITOR and adjust setpoints and input values.
- Highlight GEN OVER/UNDER FREQ and adjust setpoints and values.
- Highlight GEN OVER/UNDER VOLT and adjust setpoints and values.
- Highlight SPARE ANALOG INPUT; enable and configure if used.
- Highlight EVENT RESPONSE CONFIG and select the event responses and checkboxes.
Full service-parts list: Caterpillar 3516 →, Caterpillar EMCP 3 →
Source: Caterpillar service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.