Briggs & Stratton — High Voltage Wiring Interconnections

Installation · Transfer switch, main distribution panel, utility, generator

From a Briggs & Stratton service manual — check it applies to your exact model before use.

Browse Briggs & Stratton generators & specs →

Before you start

  • Low voltage wire cannot be installed in same conduit as power voltage wiring

Procedure

  1. Ensure utility power is OFF
  2. Connect utility feeder conductors to 'UTILITY CONNECTION' terminals
  3. Connect utility Neutral conductor to 'NEUTRAL' terminal
  4. Connect main breaker panel feeder conductors to 'LOAD CONNECTION' terminals
  5. Connect main breaker panel Neutral conductor to 'NEUTRAL' terminal
  6. Connect main breaker panel Ground conductor to 'GND' terminal
  7. Connect generator feeder conductors to 'GENERATOR CONNECTION' terminals, passing each conductor through a current transformer
  8. Plug current transformer leads into CT1 and CT2 on control module
  9. Connect Neutral conductor from generator control panel to 'NEUTRAL' terminal
  10. Connect generator Ground conductor to 'GND' terminal
  11. Connect generator 'UTILITY 240 VAC' terminals to transfer switch 'UTILITY 240 VAC' terminals using minimum #14 AWG conductors
  12. Tighten all wire connections/fasteners to proper torque per enclosure label

Specs & values

  • minimum #14 AWG conductors for UTILITY 240 VAC connection

Source: Briggs & Stratton service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.