Briggs & Stratton — Before Performing Generator Maintenance

Maintenance · Generator electrical system

From a Briggs & Stratton service manual — check it applies to your exact model before use.

Browse Briggs & Stratton generators & specs →

Before you start

  • Utility voltage is present at generator controller.
  • Disconnect all power before servicing controller.

Procedure

  1. Set generator circuit breaker to OFF position.
  2. Press controller OFF button.
  3. Remove 15 Amp fuse from controller.
  4. Disconnect power from transfer switch by removing its fuses.
  5. Perform maintenance.
  6. Reinstall fuses in transfer switch.
  7. Replace 15 Amp fuse in controller.
  8. Set circuit breaker to ON.
  9. Reset exercise timer.

Specs & values

  • 15 Amp ATO fuse type required

Source: Briggs & Stratton service manual. Steps and values are as documented; always cross-check against the official manual and any later revisions for your exact serial number before servicing.