| AC Sens Loss | AC Sensing Lost | In Auto mode, generator output AC sensing is lost. Detection begins 10 seconds after crank disconnect. | Warning | Contact authorized distributor/dealer for service |
| AC Sens Loss Shutdown | Loss of AC sensing shutdown | Less than 5% of rated voltage measured on Phase A for 3 seconds in AUTO | Shutdown | Check loose wiring and connections; check all AC leads; troubleshoot alternator |
| AC Sens Loss Shutdwn | Loss of AC sensing shutdown | Controller shut down the generator because there was less than 5% of rated voltage measured on Phase A for 3 seconds, only in AUTO. | Shutdown | Check for loose wiring and connections. Check all AC leads. Troubleshoot alternator. |
| AC Sens Loss Warning | Loss of AC sensing warning | Less than 5% of rated voltage on Phase A for 1 second, 10 seconds after crank disconnect | Warning | Check loose wiring and connections; check all AC leads; troubleshoot alternator |
| AF | Auxiliary fault input shutdown | Shutdown initiated by pushing the emergency stop switch (TRES models only). Not used on RES models. | Shutdown | Check the position of the emergency stop button. (TRES models only) |
| ATS ComError | ATS Communication Error | Warning is displayed if ATS interface connection is lost | Warning | Check communication wiring between transfer switch interface board and generator set. |
| ATS ComError Warning | ATS communication error | Controller lost communication with the RXT ATS | Warning | Check connection to ATS module |
| ATS PhaseRot | ATS PhaseRot | Transfer switch phase rotation does not match; ATS will not transfer | Warning | Correct the ATS connection. Refer to the ATS Installation manual, wiring diagrams, and labels on the transfer switch. |
| Accy PwrOver | Accessory Power Overload | An over current fault (short circuit) on the accessory controller power output | Warning | Contact authorized distributor/dealer for service |
| Accy PwrOver Warning | Accy PwrOver Warning | An over current fault (short circuit) on the accessory controller power output. | Warning | Contact an authorized distributor/dealer for service |
| AccyPwrOver Warning | Accessory Power Overload | Overcurrent fault (short circuit) on the accessory controller power output | Warning | Check wiring to RBUS accessories; troubleshoot RBUS accessories |
| Advanced Diagnostic | Advanced Diagnostic | Shutdown during the reduced speed portion of an exercise. Event history shows Advanced Diagnostic Active. Engine restarts, runs at full speed for 2 minutes, and stops. Controller returns to AUTO mode. | Shutdown | If the generator set does not restart and return to AUTO, check for other faults that prevent generator set operation. |
| Aux Input | Auxiliary Input | Optional customer-connected input (from PIM) is closed | Shutdown | Check customer-supplied equipment. |
| Aux Input Shutdwn | Auxiliary input shutdown | Digital input for a custom shutdown (AuxiliaryInputShutdown - PIM) was activated (low). | Shutdown | Check customer equipment connected to the PIM module. |
| Batt Chg Flt | Battery Charger Fault | Input to PIM from an external battery charger (not the built-in battery charger). | Warning | Check external battery charger. |
| Battery CRLow Warning | Battery cranking low warning | Battery voltage dropped to 11 VDC or less for 30 seconds or more. | Warning | Check engine starting battery; check battery charger DC output from RDC2 |
| Battery CrLo | Battery Crank Low | Engine starting battery voltage falls below 11 VDC for more than 10 seconds | Warning | Clears when battery voltage returns to acceptable level |
| Battery CrLo Warning | Low Cranking Battery Voltage Warning | Engine starting battery voltage falls below 11 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when battery voltage returns to acceptable level. | Warning | Check the battery rating and condition. Check the battery charger operation. Charge or replace the battery. |
| Battery High | Battery High | Engine starting battery voltage rises above 16 VDC for more than 10 seconds (inhibited during crank) | Warning | Check battery rating/condition and charger operation |
| Battery High Warning | Battery high warning | Battery voltage above the high warning setting for 10 seconds or more. | Warning | Check engine starting battery. |
| Battery Low Warning | Battery low warning | Controller measured battery voltage below low warning setting for 90 seconds or more | Warning | Check engine starting battery; check battery charger DC output from RDC2 |
| Battery Voltage High | Battery Voltage High | Engine starting battery voltage rises above 16 VDC for more than 10 seconds. Inhibited during crank cycle. Clears when voltage returns to acceptable level. | Warning | Check the battery rating and condition. Check the battery charger operation. |
| Battery Voltage Low | Battery Voltage Low | Engine starting battery voltage falls below 12.5 VDC for more than 90 seconds when engine not running. Not operative during crank cycle. Clears when voltage returns to acceptable level. | Warning | Check the battery rating and condition. Check the battery charger operation. Charge or replace the battery. |
| CC | Crank cycle | | | |
| CO-3 | | Fault displayed if the CO parameter is set incorrectly | Shutdown | |
| CO-6 | | Fault displayed if the CO parameter is set incorrectly | Shutdown | |
| Chk DateTime Warning | Check Date and Time Warning | DC power to controller interrupted and date/time may not be correct | Warning | Verify time and date settings |
| Default Pars Warning | Default Parameters Warning | Controller has been loaded with default parameters | Warning | Configure settings as required for desired operation |
| Emerg Stop Shutdwn | Emergency stop shutdown | Optional emergency stop button pressed or emergency stop leads ESS and/or ESN not connected | Shutdown | Reset the emergency stop button and clear the fault; check ESS and ESN connections; if no E-stop, connect ESS and ESN together. |
| Eng Speed High | Eng Speed High | Engine speed exceeds 115% of normal running speed for more than 0.3 seconds | Shutdown | Contact an authorized distributor/dealer for service |
| Eng Speed Low | Eng Speed Low | Engine speed drops below 85% of normal running speed for more than 3 seconds | Shutdown | Reduce the load; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists |
| Engine M/N Invalid Shutdwn | Engine model number invalid shutdown | Generator model number has not been entered. | Shutdown | Enter the generator set model number from the RDC2 keypad, or use SiteTech to select the genset model number. |
| Engine Speed High | Engine Speed High | Engine speed exceeds 115% of the normal running speed for more than 0.3 seconds. | Shutdown | Contact an authorized dealer for service. |
| Engine Speed High Shutdwn | Engine speed high shutdown | Engine speed, calculated from AC frequency, was above the high speed setting for 0.3 seconds or more. | Shutdown | Troubleshoot engine operation per the engine service manual. |
| Engine Speed Low | Engine Speed Low | Engine speed drops below 85% of the normal running speed for more than 3 seconds. | Shutdown | Reduce the load. Check enclosure thermostat and reset if tripped. Contact an authorized dealer for service. |
| Engine Speed Low Shutdwn | Engine speed low shutdown | Engine speed below the low speed setting for 3 seconds or more after crank disconnect; enclosure thermostat may have tripped. | Shutdown | Troubleshoot engine; check enclosure thermostat and reset if tripped |
| Exer Not Sch | Exercise Not Scheduled | No exercise is scheduled on the controller. | Warning | Set the exerciser per Section 3.6 |
| Frequency High | Frequency High | Governed frequency exceeds 110% of the system's frequency setpoint for more than 10 seconds. Active 10 seconds after engine start. | Shutdown | Contact an authorized distributor/dealer for service |
| Frequency High Shutdwn | Frequency high shutdown | Frequency on Phase A exceeded high frequency setting for 10 seconds | Shutdown | Troubleshoot engine operation per the engine service manual. |
| Frequency Low | Frequency Low | Governed frequency falls below 90% of the system frequency setting for more than 10 seconds, or 1 Hz below setting for more than 60 seconds. Active 10 seconds after engine start. | Shutdown | Reduce the load and restart; on 20RCA/RCAL check enclosure thermostat; contact dealer if it persists |
| Frequency Low Shutdwn | Frequency low shutdown | Frequency on Phase A was less than the low limit for 10 seconds, or 10 Hz or more less than rated for 60 seconds or more. | Shutdown | Troubleshoot engine; check and reset enclosure thermostat |
| Fuel Leak Shutdwn | Fuel Leak Shutdown | Digital input for Fuel Tank Leak Shutdown (PIM) activated (low) | Shutdown | Check customer equipment connected to the PIM module |
| Fuel Level Low Shutdwn | Fuel Level Low Shutdown | Digital input for Low Fuel Level Shutdown (PIM) activated (low) | Shutdown | Check customer equipment connected to the PIM module |
| GenBrkerOpen Warning | Generator Circuit Breaker Open | Voltage at generator set but none measured on emergency side of ATS (RXT required) | Warning | Check line circuit breaker; correct short circuits or overloading before resetting |
| Ground Fault Warning | Ground Fault Warning | Digital input for Ground Fault Warning (PIM) active (low) | Warning | Check customer equipment connected to the PIM module |
| HB | High battery voltage warning | Fault code is displayed if the engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running. Not operative during the engine crank cycle; does not inhibit engine starting. Clears when the battery voltage returns to an acceptable level. | Warning | Check the battery rating and condition; check battery charger operation. |
| HE | High engine temperature shutdown | Shutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This protective feature becomes active after the engine reaches the crank disconnect speed. | Shutdown | Check for blocked air inlets and exhaust outlets. |
| High Lube Oil Temperature Shutdown | High lube oil temperature shutdown | Oil temperature higher than 325 F (163 C). | Shutdown | See Overheats troubleshooting; check cooling |
| High Lube Oil Temperature Warning | High lube oil temperature warning | Oil temperature higher than 300 F (149 C). | Warning | See Overheats troubleshooting |
| LB | Low battery voltage warning | Fault code is displayed if the engine starting battery voltage falls below 8 VDC for a 12 VDC system or below 16 VDC for a 24 VDC system for more than 10 seconds when the engine is not running. Does not inhibit engine starting; clears when voltage returns to limits for more than 10 seconds. | Warning | Check the battery rating and condition; check battery charger operation; charge or replace battery. |
| LCL | Low coolant level | Not used on air-cooled models. | Shutdown | |
| LO P | Low oil pressure shutdown | Shutdown occurs if a low oil pressure condition exists for more than 5 seconds. Active 30 seconds after crank disconnect speed. Does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| LOC | Loss of coolant | Not used on air-cooled models. | Shutdown | |
| LOP | Low oil pressure shutdown | Shutdown occurs if low oil pressure exists for more than 5 seconds; active 30 seconds after crank disconnect speed. Does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. |
| Lo Crank Vlt | Low Cranking Voltage | Battery voltage dropped below 3.5 VDC during engine cranking. | Warning | Charge or replace the battery. |
| Lo Crank Vlt Warning | Low cranking voltage warning | During cranking, battery voltage measured less than 60% (7.2V or 14.4V) for 6 seconds or more. | Warning | Check cranking battery. |
| Locked Rotor | Locked Rotor | No engine rotation sensed during cranking; shuts down 3 seconds after detection | Shutdown | Check the battery. Check for loose connections. Contact an authorized dealer for service. |
| Locked Rotor Shutdwn | Locked rotor shutdown | No rotation of the engine or alternator was detected for 3 seconds or more during cranking. | Shutdown | Check cranking circuit; troubleshoot engine and alternator; check aux winding circuit breaker |
| Low Oil Level or Oil Pressure | Low Oil Level or Oil Pressure | Oil level switch on the 26 kW indicates low oil level. LOP switch indicates low oil pressure for more than 5 seconds. Active 30 seconds after crank disconnect. Does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if low. Check the oil level or oil pressure switch and wiring. If fault persists, do not run the generator set; contact an authorized dealer. |
| MainPwrOverL | MainPwrOverL | Main power overload; an over current fault on the controller output (short circuit). | Shutdown | Contact an authorized distributor/dealer for service |
| MainPwrOverL Shutdwn | Main power overload shutdown | Internal current limit circuit tripped, indicating an overcurrent condition on the DC power supply circuit. | Shutdown | Check crank, run, and flash relay circuits for short circuits. |
| Not In Auto Warning | Not in auto warning | The RDC2 controller is not in AUTO; generator will not start from an ATS or remote device. | Warning | Press the Auto button to ensure automatic system operation. |
| Not in Auto | Not in Auto | The generator set is not in Automatic (standby) mode. Remote start and stop commands from a transfer switch or remote switch will be ignored. | Warning | Press AUTO to place the generator set in Automatic mode, when appropriate. |
| OC | Overcrank shutdown | Shutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest. The generator set also shuts down on OC if no engine rotation is sensed during cranking; shuts down 3 seconds after the fault is detected (locked rotor). | Shutdown | Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized distributor/dealer if the problem continues. |
| OF | Overfrequency shutdown | Shutdown when governed frequency exceeds 110% of system frequency setpoint for more than 5 seconds; active 10 seconds after engine start. | Shutdown | Contact an authorized distributor/dealer for service if the problem continues. |
| OS | Overspeed shutdown | Shutdown occurs if the engine speed exceeds 115% of the normal running speed for more than 1 second. | Shutdown | Contact an authorized distributor/dealer for service if the problem continues. |
| OU | Overvoltage shutdown | Shutdown occurs if voltage exceeds 120% of system nominal voltage for more than 2 seconds. | Shutdown | Contact an authorized distributor/dealer for service. |
| Oil Press Low | Oil Pressure Low | The LOP switch indicates low oil pressure for more than 5 seconds. Function becomes active 30 seconds after crank disconnect (30 second inhibit). The low oil pressure shutdown does not protect against low oil level. | Shutdown | Check for leaks in the lubrication system. Check the oil level and add oil if the level is low. Check the oil pressure switch and wiring. If the fault persists, do not run the generator set. Contact an authorized dealer for service. |
| Oil Pressure Low Shutdwn | Oil Pressure Low Shutdown | The low oil pressure switch was closed for 5 seconds or more; inhibited until 30 seconds after crank disconnect. | Shutdown | Check for oil leaks; check oil level and add oil; check oil pressure sensor |
| Oil Pressure OpenCR Warning | Oil pressure open circuit warning | Oil pressure switch closure has not been detected after shutdown. | Warning | Check the oil pressure switch connection. Test the LOP switch. |
| Over Crank | Over Crank | Three unsuccessful starting attempts. | Shutdown | Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized dealer for service. |
| Over Crank Shutdwn | Overcrank shutdown | The engine did not start during the crank cycle (15 second time delay). | Shutdown | Check the alternator, fuel supply, cranking circuit, cranking battery; troubleshoot engine. |
| RBUS ComError Warning | RBUS communication error warning | The controller has lost communication with an RBUS device that had previously been communicating properly. | Warning | Check connection to the RBUS device. |
| SCF0 | Software Communication Fault 0 | Indicates a software or communication problem within the controller. | Shutdown | Replace the controller. Contact an authorized distributor/dealer for service. |
| Spd Sens Flt | Speed Sensor Fault | Engine speed sensor has failed or engine stalled. | Shutdown | Contact an authorized distributor/dealer for service |
| Spd Sens Flt Shutdwn | Speed sensor fault shutdown | The speed signal was lost; also occurs if the engine stalls. | Shutdown | Check leads 55, 66, F+, and F- between the alternator and the controller; check the engine. |
| UF | Underfrequency shutdown | Shutdown when governed frequency falls below 90% of nominal system frequency for more than 5 seconds; active 10 seconds after engine start. (ADC-RES: below 54 Hz.) | Shutdown | Reduce the load and restart the generator set; contact distributor/dealer if problem continues |
| UU | Undervoltage shutdown | Shutdown occurs if voltage falls below 80% of the nominal system voltage for more than 10 seconds. | Shutdown | Reduce the load and restart the generator set; contact distributor/dealer if problem continues |
| Volts L1-L2 (AB) High Shutdwn | Volts L1-L2 High Shutdown | Voltage from Phase A to Phase B exceeded the high limit for longer than the 2 second delay setting. | Shutdown | Troubleshoot alternator. |
| Volts L1-L2 (AB) Low Shutdwn | Volts L1-L2 Low Shutdown | Voltage from Phase A to Phase B was greater than 5% of rated but less than the low voltage setting for longer than the 10 second delay; enclosure thermostat may have tripped. | Shutdown | Troubleshoot alternator; check and reset enclosure thermostat |