Cummins/Onan DQPAA Generator Set

The Cummins/Onan DQPAA is a 600 kW (750 kVA) Diesel standby generator set powered by a Cummins/Onan QSK19-G8 engine. It is available at 110/190 V, 120/208 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 255/440 V and 277/480 V, A (U), B (V), C (W) and 60 Hz. It holds about 68.1 L (18.0 gal) of oil and 95 L (25.1 gal) of coolant, with a maximum ambient rating of 52 °C. The set measures 4629×1742×2189 mm (182.2×68.6×86.2 in) and weighs about 5211 kg (11488 lb).

600 kW
Standby
68.1 L
Oil capacity
2
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 600–605 kW Diesel generators →

Compare with other 600–605 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power600 kW
Standby kVA750
Prime power545 kW
EmissionsEPA NSPS Stationary Emergency Tier 2
ControllerPowerCommand
Oil capacity68.1 L
Voltage options110/190 V, 120/208 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 255/440 V, 277/480 V
PhaseA (U), B (V), C (W)
Coolant capacity95 L
Max ambient52 °C
Dimensions (L×W×H)4629×1742×2189 mm
Dry weight5211 kg

Engine

Cummins/Onan QSK19-G8
Oil capacity68.1 L
AspirationTurbocharged and charged after-cooled (air- to-air)
Rated speed1800 rpm

Filters for the Cummins/Onan QSK19-G8

5

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

SystemFilterDescriptionCross-references
Oil filterP553000Lube Filter, Spin-On Full FlowCUMMINS 3318853, CUMMINS 3825970, NAPA 1748, NAPA 1748XD FridayParts $125.00
Oil filterP550777Lube Filter, Spin-On BypassCUMMINS 3021658, CUMMINS 33004232, NAPA 1749, BALDWIN B7577 FridayParts $43.56
Fuel / water separatorP551000Fuel Filter, Water Separator Spin-On Twist&DrainCUMMINS 3161407, CUMMINS 3329289, NAPA 3406, BALDWIN BF1259 FridayParts $99.00

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Coolant filterP552072Coolant Filter, Spin-On Sca PlusCUMMINS 3100305, CUMMINS 3300900, NAPA 4072, IMPERIAL 04WF2072 buy
Coolant filterP552073Coolant Filter, Spin-On Sca PlusCUMMINS 209605, CUMMINS 299082, NAPA 4073, IMPERIAL 04WF2073 buy

Filters & service parts

model family
ItemSpecCapacityPart #Interval
Air filterDry replaceable element with restriction indicator—
Fuel filterDual element, 10 micron filtration, spin-on fuel filters with 15 micron water separator—
Oil filter—
Battery—
Belt—
Coolant492.0—
Oil334.0—
Spark plug—

Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.

Service specifications

39
TypeItemValueUnitCondition
OtherAC waveform THD (THDV)< 5%no load to full linear load
OtherBMEP at set rated load (prime)1885kPaprime rating
OtherBMEP at set rated load (standby)2109kPastandby rating
OtherBreaker fail to synchronize default time delay120sadjustable 10–900 s
OtherDerate above 1402 m (4600 ft) / 40 °C4.5% per 305 m (1000 ft) and 11.0% per 10 °C (18 °F)standby and prime
OtherHigh AC voltage shutdown default110%% of nominal voltagefor 10 s; adjustable 105–125%, 0.1–10 s
OtherInstantaneous pickup (Ii) range (Micrologic 3.0 and 5.0)1.5–12 x Inx In
OtherLong-time delay tr0.5–24sat 6 x Ir
OtherLong-time pickup (Ir) adjustment range0.4–1.0 x Inx Insensor plug rating In
OtherLow AC voltage shutdown default85%% of reference voltagefor 10 s; adjustable 50–95%, 2–20 s
OtherOver frequency shutdown/warning default6Hz above nominalfor 20 s, disabled; adjustable 2–10 Hz above set point, 1–20 s
OtherOver load (kW) warning default105%% of rated kWadjustment range 80–140%, 0–120 s delay; default 60 s
OtherPiston speed11.4m/s
OtherReverse Var shutdown default20%% of rated Varfor 10 s; adjustable 15–50%, 10–60 s
OtherReverse power shutdown default10%% of standby kWfor 3 s; adjustable 5–20%, 1–15 s
OtherShort circuit protection threshold175%% of ratingoutput current on any phase
OtherTelephone Harmonic Factor (THF)< 3
OtherTelephone Influence Factor (TIF)< 50per NEMA MG1-22.43
OtherUnder frequency shutdown default6Hz below referencefor 10 s; adjustable 2–10 Hz below set point, 5–20 s
OtherWire stripping length1.38 In (35 mm)in
PressureMaximum air cleaner restriction6.2kPa
PressureMaximum back pressure6.8kPaexhaust
PressureMaximum cooling air flow static restriction0.12kPa
PressureMaximum fuel inlet restriction30kPa
PressureMaximum fuel return line restriction34kPa
SpeedFrequency regulationIsochronous
SpeedOverspeed limit2100 ±50rpm
SpeedRandom frequency variation± 0.25%
SpeedRated speed1800rpm60 Hz
TemperatureAmbient design (standard set-mounted radiator)50°C
TemperatureExhaust temperature at set rated load (prime)463°Cprime
TemperatureExhaust temperature at set rated load (standby)469°Cstandby
TemperatureMaximum aftercooler inlet temp49°C
TemperatureMaximum fuel inlet temperature71°C
TemperatureMaximum jacket water outlet temp (remote radiator)104°Cstandby
TorqueCircuit breaker terminal tightening torque (AWG 1/0...750 kcmil)548.75 Lbf.In (62 N.m)Lbf.In0.08…0.62 in² (50…400 mm²)
VoltageRandom voltage variation± 0.5%
VoltageStandard temperature rise150°CStandby at 40 °C ambient
VoltageVoltage regulation, no load to full load± 0.5%

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
FuelASTM D975 No. 2-DASTM D975Cetane number: 40-50. 300-500 ppm Sulfur. Fuel inlet temperature 40°C (104°F) reference.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

10
CodeNameMeaningSeverityAction
27Low AC voltage shutdownVoltage on any phase has dropped below a preset value.ShutdownAdjustable 50-95% of reference voltage, time delay 2-20 seconds; default 85% for 10 seconds.
32Reverse power shutdownReverse power detected.ShutdownAdjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds.
40Reverse Var shutdownReverse reactive power detected.ShutdownAdjustable 15-50% of rated Var output, delay 10-60 seconds; default 20%, 10 seconds.
46Negative sequence overcurrent warningExcessive imbalances in the three phase load currents and/or power factors.WarningControl protects generator from damage due to phase imbalance.
51Overcurrent warning/shutdownImplementation of the thermal damage curve with instantaneous trip level based on CT ratio and application power rating.ShutdownAmpSentry protective relay action; see document R1053 time over current curve.
51GGround fault overcurrentDetects a ground fault via external ground fault relay contact input or measured ground current from external CT.ShutdownTime delays and thresholds adjustable via InPower or HMI.
59High AC voltage shutdownOutput voltage on any phase exceeds preset values; trip time inversely proportional to amount above threshold.ShutdownAdjustable 105-125% of nominal voltage, time delay 0.1-10 seconds; default 110% for 10 seconds.
81 uUnder Frequency ShutdownGenset output frequency cannot be maintained. Adjustable 2-10 Hz below reference governor set point, time delay 5-20 s. Default 6 Hz, 10 s.Shutdown
81oOver frequency shutdown/warningGenset is operating at a potentially damaging frequency level.WarningAdjustable 2-10 Hz above nominal governor set point, 1-20 second delay; default 6 Hz, 20 seconds, disabled.
81uUnder frequency shutdownGenset output frequency cannot be maintained.ShutdownAdjustable 2-10 Hz below reference governor set point, 5-20 second delay; default 6 Hz, 10 seconds.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

3
Trip Unit Operation Verification diagnostic

Tools: Trip unit test kit

  1. Connect a test kit to the trip unit test plug receptacle.
  2. Perform verification tests per instructions shipped with the test kit to verify trip unit functions.
Battery replacement / battery rack installation maintenance
  1. Isolate DC supply before working on battery connections.
  2. Install battery rack with hold-down, floor standing.
  3. Install battery with minimum 2200 amps capacity at -18 °C to 0 °C.
  4. Verify 24 volt negative ground connection.
Trip Unit Switch Adjustment operation

⚠ Wait a minimum of 15 minutes after circuit breaker trips before resetting to allow thermal imaging to reset completely to zero.

Tools: Wire seal MICROTUSEAL

  1. Open switch cover.
  2. Adjust the appropriate switches to desired values.
  3. Replace switch cover.
  4. Use wire seal MICROTUSEAL, if necessary, to provide tamper evidence.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
12470-138003Wye, 3-phaseWinding no. 6062Temp rise 125/105/80 °C; ADS-521; feature code B448; max surge kVA 91
220/38036 leads6Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C
240/41636 leads6Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C
254/44036 leads6Winding no. 312; 125°C rise rating 2000 kW / 2500 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C
277/48036 leads6Winding no. 312; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C
277/4803Wye, 4 WireFeature code R002-2 Voltage-277/480, 3 Phase, Wye, 4 Wire
346/60036 leads6Winding no. 07; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00220 Ohms; rotor resistance 2.31 Ohms @22°C
3803Wye, 3-phaseWinding no. 7327Temp rise 150/125/105 °C; ADS-335; feature code B595; max surge kVA 312
41603Wye, 3-phaseWinding no. 6307Temp rise 125/105/80 °C; ADS-324; feature code B467; max surge kVA 51
4803Wye, 3-phaseWinding no. 7361Temp rise 125/105/80 °C; ADS-333; feature code B462; max surge kVA 312
6003Wye, 3-phaseWinding no. 7361Temp rise 125/105/80 °C; ADS-333; feature code B465; max surge kVA 07

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Cummins/Onan DQPAA?

The Cummins/Onan DQPAA is rated 600 kW standby (750.0 kVA).

Which engine powers the Cummins/Onan DQPAA?

The Cummins/Onan DQPAA is powered by the Cummins/Onan QSK19-G8 engine.

What kind of fuel does the Cummins/Onan DQPAA run on?

The Cummins/Onan DQPAA runs on Diesel.

What's the oil capacity on a Cummins/Onan DQPAA?

The Cummins/Onan QSK19-G8 engine in the Cummins/Onan DQPAA has an oil capacity of 68.1 liters.

What is the coolant capacity of the Cummins/Onan DQPAA?

The Cummins/Onan DQPAA cooling system holds 95 liters (25.1 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Cummins/Onan DQPAA?

The Cummins/Onan DQPAA is rated 545 kW prime (681 kVA), against 600 kW standby.

What is the dry weight of the Cummins/Onan DQPAA?

The Cummins/Onan DQPAA has a dry weight of 5211 kg (11488 lb).

What voltages is the Cummins/Onan DQPAA available in?

The Cummins/Onan DQPAA is offered in 110/190 V, 120/208 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, A (U), B (V), C (W)-phase.

Repair guides

2

Step-by-step procedures compiled from the Cummins/Onan service manual for this model.

Parts

17
Part #DescriptionQtySystem
338-4386Harness, Meter1Wiring Amazon eBay $1500.00
A029G375Harness, Relay1Wiring Amazon eBay
526-0100Washer, Flat (9/16' ID x2Service part / kit Amazon eBay
800-0093Screw, Hex Head1Service part / kit Amazon eBay
800-0094Screw, Cap – Hex Head (1/2–13 x 2")1Service part / kit Amazon eBay
821-2096-03Screw, Flange Head Lock2Service part / kit Amazon eBay
821-6003-02Screw, Cap - Hex Head (M8 x 1.25 x 25mm)2Service part / kit Amazon eBay
851-0023Washer2Service part / kit Amazon eBay
862-0016Nut, Hex6Service part / kit Amazon eBay
870-2054Nut, Flanged Locking (M6)2Service part / kit Amazon eBay $28.90
A040A357Panel, Cover1Service part / kit Amazon eBay
A040B391Busbar, Ground1Service part / kit Amazon eBay
A040J745Bracket1Service part / kit Amazon eBay
A041A931Busbar, Copper1Service part / kit Amazon eBay
A041Z271Panel, Terminal1Service part / kit Amazon eBay
A042X594Busbar, Copper1Service part / kit Amazon eBay
A043K271Box, Circuit Breaker1Service part / kit Amazon eBay $210.95

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime155.241.0
Prime25%46.212.2
Prime50%80.321.2
Prime100%155.241.0
Standby25%49.213.0
Standby50%87.023.0
Standby75%123.033.5
Standby100%171.845.4

Available documents

Spec sheet — Cummins-600-DQPAA (Cummins/Onan)Spec sheet — NAS-5751-EN-DC60 (Cummins/Onan)Spec sheet — NAS-5751-EN (Cummins/Onan)Spec sheet — New-Cummins-DQKAA-submittal (Cummins/Onan)Parts manual — A045S264 I7 201610 (Cummins/Onan)

This page was generated from the 5 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.