Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 600 kW |
| Standby kVA | 750 |
| Prime power | 545 kW |
| Emissions | EPA NSPS Stationary Emergency Tier 2 |
| Controller | PowerCommand |
| Oil capacity | 68.1 L |
| Voltage options | 110/190 V, 120/208 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, 255/440 V, 277/480 V |
| Phase | A (U), B (V), C (W) |
| Coolant capacity | 95 L |
| Max ambient | 52 °C |
| Dimensions (L×W×H) | 4629×1742×2189 mm |
| Dry weight | 5211 kg |
Engine
| Oil capacity | 68.1 L |
|---|---|
| Aspiration | Turbocharged and charged after-cooled (air- to-air) |
| Rated speed | 1800 rpm |
Filters for the Cummins/Onan QSK19-G8
5Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P553000 | Lube Filter, Spin-On Full Flow | CUMMINS 3318853, CUMMINS 3825970, NAPA 1748, NAPA 1748XD | FridayParts $125.00 |
| Oil filter | P550777 | Lube Filter, Spin-On Bypass | CUMMINS 3021658, CUMMINS 33004232, NAPA 1749, BALDWIN B7577 | FridayParts $43.56 |
| Fuel / water separator | P551000 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 3161407, CUMMINS 3329289, NAPA 3406, BALDWIN BF1259 | FridayParts $99.00 |
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Coolant filter | P552072 | Coolant Filter, Spin-On Sca Plus | CUMMINS 3100305, CUMMINS 3300900, NAPA 4072, IMPERIAL 04WF2072 | buy |
| Coolant filter | P552073 | Coolant Filter, Spin-On Sca Plus | CUMMINS 209605, CUMMINS 299082, NAPA 4073, IMPERIAL 04WF2073 | buy |
Filters & service parts
model family| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry replaceable element with restriction indicator | — | |||
| Fuel filter | Dual element, 10 micron filtration, spin-on fuel filters with 15 micron water separator | — | |||
| Oil filter | — | ||||
| Battery | — | ||||
| Belt | — | ||||
| Coolant | 492.0 | — | |||
| Oil | 334.0 | — | |||
| Spark plug | — |
Compiled from this model's family documentation — may include parts for closely-related variants. Confirm the exact part for your serial number.
Service specifications
39| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | AC waveform THD (THDV) | < 5 | % | no load to full linear load |
| Other | BMEP at set rated load (prime) | 1885 | kPa | prime rating |
| Other | BMEP at set rated load (standby) | 2109 | kPa | standby rating |
| Other | Breaker fail to synchronize default time delay | 120 | s | adjustable 10–900 s |
| Other | Derate above 1402 m (4600 ft) / 40 °C | 4.5% per 305 m (1000 ft) and 11.0% per 10 °C (18 °F) | standby and prime | |
| Other | High AC voltage shutdown default | 110% | % of nominal voltage | for 10 s; adjustable 105–125%, 0.1–10 s |
| Other | Instantaneous pickup (Ii) range (Micrologic 3.0 and 5.0) | 1.5–12 x In | x In | |
| Other | Long-time delay tr | 0.5–24 | s | at 6 x Ir |
| Other | Long-time pickup (Ir) adjustment range | 0.4–1.0 x In | x In | sensor plug rating In |
| Other | Low AC voltage shutdown default | 85% | % of reference voltage | for 10 s; adjustable 50–95%, 2–20 s |
| Other | Over frequency shutdown/warning default | 6 | Hz above nominal | for 20 s, disabled; adjustable 2–10 Hz above set point, 1–20 s |
| Other | Over load (kW) warning default | 105% | % of rated kW | adjustment range 80–140%, 0–120 s delay; default 60 s |
| Other | Piston speed | 11.4 | m/s | |
| Other | Reverse Var shutdown default | 20% | % of rated Var | for 10 s; adjustable 15–50%, 10–60 s |
| Other | Reverse power shutdown default | 10% | % of standby kW | for 3 s; adjustable 5–20%, 1–15 s |
| Other | Short circuit protection threshold | 175% | % of rating | output current on any phase |
| Other | Telephone Harmonic Factor (THF) | < 3 | ||
| Other | Telephone Influence Factor (TIF) | < 50 | per NEMA MG1-22.43 | |
| Other | Under frequency shutdown default | 6 | Hz below reference | for 10 s; adjustable 2–10 Hz below set point, 5–20 s |
| Other | Wire stripping length | 1.38 In (35 mm) | in | |
| Pressure | Maximum air cleaner restriction | 6.2 | kPa | |
| Pressure | Maximum back pressure | 6.8 | kPa | exhaust |
| Pressure | Maximum cooling air flow static restriction | 0.12 | kPa | |
| Pressure | Maximum fuel inlet restriction | 30 | kPa | |
| Pressure | Maximum fuel return line restriction | 34 | kPa | |
| Speed | Frequency regulation | Isochronous | ||
| Speed | Overspeed limit | 2100 ±50 | rpm | |
| Speed | Random frequency variation | ± 0.25 | % | |
| Speed | Rated speed | 1800 | rpm | 60 Hz |
| Temperature | Ambient design (standard set-mounted radiator) | 50 | °C | |
| Temperature | Exhaust temperature at set rated load (prime) | 463 | °C | prime |
| Temperature | Exhaust temperature at set rated load (standby) | 469 | °C | standby |
| Temperature | Maximum aftercooler inlet temp | 49 | °C | |
| Temperature | Maximum fuel inlet temperature | 71 | °C | |
| Temperature | Maximum jacket water outlet temp (remote radiator) | 104 | °C | standby |
| Torque | Circuit breaker terminal tightening torque (AWG 1/0...750 kcmil) | 548.75 Lbf.In (62 N.m) | Lbf.In | 0.08…0.62 in² (50…400 mm²) |
| Voltage | Random voltage variation | ± 0.5 | % | |
| Voltage | Standard temperature rise | 150 | °C | Standby at 40 °C ambient |
| Voltage | Voltage regulation, no load to full load | ± 0.5 | % |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | ASTM D975 No. 2-D | ASTM D975 | Cetane number: 40-50. 300-500 ppm Sulfur. Fuel inlet temperature 40°C (104°F) reference. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
10| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 27 | Low AC voltage shutdown | Voltage on any phase has dropped below a preset value. | Shutdown | Adjustable 50-95% of reference voltage, time delay 2-20 seconds; default 85% for 10 seconds. |
| 32 | Reverse power shutdown | Reverse power detected. | Shutdown | Adjustment range 5-20% of standby kW rating, delay 1-15 seconds; default 10%, 3 seconds. |
| 40 | Reverse Var shutdown | Reverse reactive power detected. | Shutdown | Adjustable 15-50% of rated Var output, delay 10-60 seconds; default 20%, 10 seconds. |
| 46 | Negative sequence overcurrent warning | Excessive imbalances in the three phase load currents and/or power factors. | Warning | Control protects generator from damage due to phase imbalance. |
| 51 | Overcurrent warning/shutdown | Implementation of the thermal damage curve with instantaneous trip level based on CT ratio and application power rating. | Shutdown | AmpSentry protective relay action; see document R1053 time over current curve. |
| 51G | Ground fault overcurrent | Detects a ground fault via external ground fault relay contact input or measured ground current from external CT. | Shutdown | Time delays and thresholds adjustable via InPower or HMI. |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; trip time inversely proportional to amount above threshold. | Shutdown | Adjustable 105-125% of nominal voltage, time delay 0.1-10 seconds; default 110% for 10 seconds. |
| 81 u | Under Frequency Shutdown | Genset output frequency cannot be maintained. Adjustable 2-10 Hz below reference governor set point, time delay 5-20 s. Default 6 Hz, 10 s. | Shutdown | |
| 81o | Over frequency shutdown/warning | Genset is operating at a potentially damaging frequency level. | Warning | Adjustable 2-10 Hz above nominal governor set point, 1-20 second delay; default 6 Hz, 20 seconds, disabled. |
| 81u | Under frequency shutdown | Genset output frequency cannot be maintained. | Shutdown | Adjustable 2-10 Hz below reference governor set point, 5-20 second delay; default 6 Hz, 10 seconds. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
3Trip Unit Operation Verification diagnostic
Tools: Trip unit test kit
- Connect a test kit to the trip unit test plug receptacle.
- Perform verification tests per instructions shipped with the test kit to verify trip unit functions.
Battery replacement / battery rack installation maintenance
- Isolate DC supply before working on battery connections.
- Install battery rack with hold-down, floor standing.
- Install battery with minimum 2200 amps capacity at -18 °C to 0 °C.
- Verify 24 volt negative ground connection.
Trip Unit Switch Adjustment operation
⚠ Wait a minimum of 15 minutes after circuit breaker trips before resetting to allow thermal imaging to reset completely to zero.
Tools: Wire seal MICROTUSEAL
- Open switch cover.
- Adjust the appropriate switches to desired values.
- Replace switch cover.
- Use wire seal MICROTUSEAL, if necessary, to provide tamper evidence.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 12470-13800 | 3 | Wye, 3-phase | Winding no. 6062 | Temp rise 125/105/80 °C; ADS-521; feature code B448; max surge kVA 91 |
| 220/380 | 3 | 6 leads | 6 | Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C |
| 240/416 | 3 | 6 leads | 6 | Winding no. 13; 125°C rise rating 2004 kW / 2505 kVA; stator resistance L-L 0.00102 Ohms; rotor resistance 2.31 Ohms @22°C |
| 254/440 | 3 | 6 leads | 6 | Winding no. 312; 125°C rise rating 2000 kW / 2500 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C |
| 277/480 | 3 | 6 leads | 6 | Winding no. 312; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00152 Ohms; rotor resistance 2.31 Ohms @22°C |
| 277/480 | 3 | Wye, 4 Wire | Feature code R002-2 Voltage-277/480, 3 Phase, Wye, 4 Wire | |
| 346/600 | 3 | 6 leads | 6 | Winding no. 07; 125°C rise rating 2080 kW / 2600 kVA; stator resistance L-L 0.00220 Ohms; rotor resistance 2.31 Ohms @22°C |
| 380 | 3 | Wye, 3-phase | Winding no. 7327 | Temp rise 150/125/105 °C; ADS-335; feature code B595; max surge kVA 312 |
| 4160 | 3 | Wye, 3-phase | Winding no. 6307 | Temp rise 125/105/80 °C; ADS-324; feature code B467; max surge kVA 51 |
| 480 | 3 | Wye, 3-phase | Winding no. 7361 | Temp rise 125/105/80 °C; ADS-333; feature code B462; max surge kVA 312 |
| 600 | 3 | Wye, 3-phase | Winding no. 7361 | Temp rise 125/105/80 °C; ADS-333; feature code B465; max surge kVA 07 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Cummins/Onan DQPAA?
The Cummins/Onan DQPAA is rated 600 kW standby (750.0 kVA).
Which engine powers the Cummins/Onan DQPAA?
The Cummins/Onan DQPAA is powered by the Cummins/Onan QSK19-G8 engine.
What kind of fuel does the Cummins/Onan DQPAA run on?
The Cummins/Onan DQPAA runs on Diesel.
What's the oil capacity on a Cummins/Onan DQPAA?
The Cummins/Onan QSK19-G8 engine in the Cummins/Onan DQPAA has an oil capacity of 68.1 liters.
What is the coolant capacity of the Cummins/Onan DQPAA?
The Cummins/Onan DQPAA cooling system holds 95 liters (25.1 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Cummins/Onan DQPAA?
The Cummins/Onan DQPAA is rated 545 kW prime (681 kVA), against 600 kW standby.
What is the dry weight of the Cummins/Onan DQPAA?
The Cummins/Onan DQPAA has a dry weight of 5211 kg (11488 lb).
What voltages is the Cummins/Onan DQPAA available in?
The Cummins/Onan DQPAA is offered in 110/190 V, 120/208 V, 127/220 V, 139/240 V, 220/380 V, 240/416 V, A (U), B (V), C (W)-phase.
Repair guides
2Step-by-step procedures compiled from the Cummins/Onan service manual for this model.
Parts
17| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 338-4386 | Harness, Meter | 1 | Wiring | Amazon eBay $1500.00 |
| A029G375 | Harness, Relay | 1 | Wiring | Amazon eBay |
| 526-0100 | Washer, Flat (9/16' ID x | 2 | Service part / kit | Amazon eBay |
| 800-0093 | Screw, Hex Head | 1 | Service part / kit | Amazon eBay |
| 800-0094 | Screw, Cap – Hex Head (1/2–13 x 2") | 1 | Service part / kit | Amazon eBay |
| 821-2096-03 | Screw, Flange Head Lock | 2 | Service part / kit | Amazon eBay |
| 821-6003-02 | Screw, Cap - Hex Head (M8 x 1.25 x 25mm) | 2 | Service part / kit | Amazon eBay |
| 851-0023 | Washer | 2 | Service part / kit | Amazon eBay |
| 862-0016 | Nut, Hex | 6 | Service part / kit | Amazon eBay |
| 870-2054 | Nut, Flanged Locking (M6) | 2 | Service part / kit | Amazon eBay $28.90 |
| A040A357 | Panel, Cover | 1 | Service part / kit | Amazon eBay |
| A040B391 | Busbar, Ground | 1 | Service part / kit | Amazon eBay |
| A040J745 | Bracket | 1 | Service part / kit | Amazon eBay |
| A041A931 | Busbar, Copper | 1 | Service part / kit | Amazon eBay |
| A041Z271 | Panel, Terminal | 1 | Service part / kit | Amazon eBay |
| A042X594 | Busbar, Copper | 1 | Service part / kit | Amazon eBay |
| A043K271 | Box, Circuit Breaker | 1 | Service part / kit | Amazon eBay $210.95 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 155.2 | 41.0 | |
| Prime | 25% | 46.2 | 12.2 |
| Prime | 50% | 80.3 | 21.2 |
| Prime | 100% | 155.2 | 41.0 |
| Standby | 25% | 49.2 | 13.0 |
| Standby | 50% | 87.0 | 23.0 |
| Standby | 75% | 123.0 | 33.5 |
| Standby | 100% | 171.8 | 45.4 |
Available documents
This page was generated from the 5 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.