Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 404 kW |
| Standby kVA | 1402 |
| Prime power | 368 kW |
| Emissions | Tier-3 |
| Controller | Digital auto-start microprocessor based control panel with remote start capability |
| Oil capacity | 30.0 L |
| Alternator | Stamford/AvK HCI534 (4-pole, Class H insulation) |
| Voltage options | 120/208 V, 120/240 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Rated current | 1402 A |
| Power factor | 0.8 |
| Circuit breaker | 1402 A |
| Battery group | 4D |
| Battery cranking | 1000 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 44 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 3238×1219×1689 mm |
| Dry weight | 3405 kg |
| Fuel tank | 2535.6 L |
| Tank runtime | 24 hr |
Engine
| Oil capacity | 30.0 L |
|---|---|
| Coolant capacity | 44.0 L |
| Displacement | 12.78 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Simson-Maxwell SVW400 T6-T3?
The Simson-Maxwell SVW400 T6-T3 is rated 404 kW standby (1402.0 kVA).
What engine does the Simson-Maxwell SVW400 T6-T3 use?
The Simson-Maxwell SVW400 T6-T3 is powered by the Volvo Penta TAD1353GE engine.
What fuel does the Simson-Maxwell SVW400 T6-T3 use?
The Simson-Maxwell SVW400 T6-T3 runs on Diesel.
What is the oil capacity of the Simson-Maxwell SVW400 T6-T3?
The Volvo Penta TAD1353GE engine in the Simson-Maxwell SVW400 T6-T3 has an oil capacity of 30.0 liters.
What alternator does the Simson-Maxwell SVW400 T6-T3 use?
The Simson-Maxwell SVW400 T6-T3 uses a Stamford/AvK HCI534 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 34.3 | |
| Prime | 50% | 55.3 | |
| Prime | 75% | 77.1 | |
| Prime | 100% | 97.0 | |
| Standby | 25% | 36.8 | |
| Standby | 50% | 59.2 | |
| Standby | 75% | 84.0 | |
| Standby | 100% | 105.6 |